EVA
Manual
6
118144
‐
001
REV.
A
UNIT/INPUT
VOLTAGE
FACTORY
CONFIGURATION
MAXIMUM
INPUT
CURRENT
PER
PHASE
180
‐
264Vac,
3
phase,
50/60Hz
3PH
(3kW,
6kW
&
12kW)
13
amps
@
3kW,
25
amps
@
6kW,
50
amps
@
12kW
180
‐
264Vac,
1
phase,
50/60Hz
1PH
(3kW
&
6kW
only)
29
amps
@
3kW,
57
amps
@
6kW
360
‐
528Vac,
3
phase,
50/60Hz
400VAC
(12kW
only)
25
amps
*Input
Voltage
Must
Be
Selected
At
Time
of
Order*
Note
:
400VAC
Option
(360
‐
528Vac)
units
do
NOT
have
a
rear
panel
circuit
breaker.
For
proper
protection
a
circuit
breaker/fuse
protected
dedicated
30
amp,
three
phase
electrical
service
must
be
provided
for
each
EVA
chassis.
Table
2.1
Input
Voltage/Current
Requirements
The
above
maximum
input
current
values
assume
a
unit
running
at
maximum
power,
operating
at
low
line
and
taking
power
supply
efficiency
and
power
factor
into
account.