background image

A.

 RJ-45 Test Jack

B.

 Test Shielded Cable

C.

 Low Battery Indicator

D.

 Test or Debug Button

E.

 Cable Select

F.

 Split Pair Testing

G.

 T56A or T56B Wiring Chart

OPERATING INSTRUCTIONS

MODEL: 

TT64200

 Cable-Test™ Cable Tester

SAFETY WARNINGS

This instruction manual contains warnings and safety rules which 

must be observed by the user to ensure safe operation of the 

instrument and retain it in safe condition. Therefore, read through 

these operating instructions before using the instrument.

!

!

WARNING

 – 

Do NoT uSE oN lIvE CIRCuITS

 

CABlE lENGTh SpECIFICATIoNS

• Min. cable length for testing:  3 feet.

• Max. cable length for testing:  600 feet.

•  Maximum Flat Cable Length for cable assembly to attach main unit 

or remote to a wall jack or patch panel: 18 inches.

Note:

 Although the TT64200 is equipped with 8 position modular 

plug jacks, cables with smaller 6 position and 4 position connectors 

may also be tested. The user should be aware that the use of smaller 

connectors will reduce the total number of jack insertions over the life 

of the product.

TESTING pATCh CABlES 

1. Connect the main unit to one end of the cable to be tested.

2. Connect Remote unit to plug at far end of cable.

3. Push the TEST button to perform test.

4. Read LEDs to determine cable wiring status.

Note: Tester will automatically turn off in 12 seconds.

TESTING INSTAllED CABlES 

1.  Using the jumper cable, connect the remote unit to the wall jack or 

patch panel port to be tested.

2.  Using the second jumper cable, connect the main unit to the other 

wall jack or patch panel port to be tested. 

3. Push the TEST button to perform test.

4. Read status of LEDs to determine cable wiring status.

 

Note: Tester will automatically turn off in 12 seconds.

TEST RESulTS 

PASS Indicators

10 Base-T

Token Ring

Shield

Crossover Cable

Two green 

LEDs on Pairs 

1-2 and 3-6. 

Both pairs 

terminated 

correctly

Two green 

LEDs on Pairs 

3-6 and 4-5. 

Both pairs 

terminated 

correctly

Green SHIELD 

LED indicates the 

Shield on the cable 

is correctly and 

continuously wired 

through the modular 

plug termination.

Four green LEDs 

on pairs 1-2,

3-6, 4-5, and 7-8. 

All four pairs 

are terminated 

correctly.

FAIl INDICAToRS

A flashing LED indicates that this wire pair has a fault. A flashing LED 

in the FAIL section will indicate which fault was detected. Multiple 

flashing LEDs indicate multiple pairs and/or multiple faults. Best 

practice is to correct cable faults until cable is verified as correct with 

appropriate green LEDs.

•  

opEN –

 There is no “OPEN” LED indication. A typical cable may have 

2, 3, or 4 pairs. OPENS are displayed as an unlit LED. The user will 

determine if a pair is present and continuous or OPEN by comparing 

the illuminated LEDs to the expected number of pairs that should 

be good. For example, when testing a 4 pair cable, three illuminated 

LEDs in the PASS area indicate the presence of an OPEN condition 

in one of the pairs.

• 

ShoRT –

 A short circuit condition exists.

•  

MISWIRE –

 Indicates the improper assignment of individual wire 

pairs to pins for the wiring schemes tested. Tester checks T568A, 

T568B, 10Base-T, and Token Ring configurations.

•  

REvERSAl –

 Reverse wiring means the pin for 

one wire in a pair is connected to the opposite pin  

for the pair in the remote jack.

•  

SplIT pAIRS –

 Split pairs occur 

when the tip (positive conductor)  

and ring (negative conductor) of  

two twisted pairs are interchanged.

•  

CRoSSovER CABlES –

 Turn the 

cable-select switch to  

crossover position. Then test  

as a normal patch cable.

Note: 

The TT64200 will check 

a fault condition in the above  

descending order before  

detecting other fault conditions.  

The detection and indication of the  

presence of a fault is handled on a  

“one-per-test” basis. Once a fault is  

corrected, it is recommended the  

cable be tested again for other faults.

DEBuG MoDE

The DEBUG mode identifies which cable pairs have a wiring fault. It 

cycles through pairs displaying a test result for one pair at a time. From 

the series of LED indications, the failed pair and fault can be identified. 

In Debug mode, a short flash on PAIR LED is the pair under test. A 

long flash on PAIR LEDs is destination of test.
To DEBUG:
1. Press and hold TEST button until all LEDs light, then release.
2.  The pair identification LEDs and the FAIL LEDs work together in 

series to identify which pair is incorrect.

3.  If a series of two green LEDs light for a pair then that pair is wired 

correctly.

4.  A green pair LED followed by a red LED in the FAIL section 

identifies which pair is incorrect and identifies the fault.

5.  DEBUG cycles through the pairs twice before automatically 

shutting off.

6. Pushing and quickly releasing the TEST button also turns tester off.

DEBuG Example #1

 The Cable Fault is a SHORT on Pair 3-6, the DEBUG 

mode LED series will be as follows:
• Pair 1-2 will flash green-green as a good pair
•  Pair 3-6 will flash green on the pair LED followed by a red on the 

SHORT LED 

• Pair 4-5 will flash green-green as a good pair
• Pair 7-8 will flash green-green as a good pair

DEBuG Example #2

 Following are some examples of potential 

sequences on pair 1-2 and interpretation of various fault conditions for 

that pair only:

1st Short

Flash

2nd long

Flash

Red Fault

LEDs

Fault Condition

1-2

1-2

No Red Light

Good Pair

1-2

None

No Red Light

Open Condition

1-2

1-2

Reversal

Pair Reversed 1-2  2-1

1-2

1-2

Short

Pin 1 Shorted to Pin 2

1-2

1-2,3-6

Short

1 or 2 shorted to 3 or 6

1-2

7-8

Miswire

Pin 1-Pin 7, Pin 2-Pin 8

1-2

7-8

Miswire, Reversal

Pin 1-Pin 8,Pin 2-Pin 7

1-2

1-2

Split Pair

Wire from 1-2 twisted with 

wire from another pair, 

continuity good

Above examples are for 1-2 pair, similar lights would relate to other pairs 

under test (short flash)

loW BATTERY INDICAToR

When the low battery LED lights, replace battery in the main unit. The 

remote unit does not use a battery.

BATTERY REplACEMENT

1.  Remove screws from back of main test unit using a #1 Philips 

screwdriver. Carefully open tester.

2. Remove old batteries.
3.  Install new 6 volt A544 1/2AA size battery or 4LR44 Button cell 

batteries.

4. Close tester and replace screws. Do not over tighten.

limited lifetime Warranty

 limited solely to repair or replacement; no 

warranty of merchantability or fitness for a particular purpose. Product 

is warrantied to be free of defects in materials and workmanship for the 

normal life of the product. In no event shall Sperry Instruments be liable 

for incidental or consequential damage.

Main unit

A

E

Remote

D

C
F

B

A

G

1
2
3
4
5
6
7
8

Split

1
2
3
4
5
6
7
8

Tip (first pair)           Ring

Split tip

Split tip

Pair 2

Pair 1

Ring

Ring

1
2
3
4
5
6
7
8

Terminal A

Terminal B

Crossover cable

1
2
3
4
5
6
7
8

Reversed

1
2
3
4
5
6
7
8

Tip

Ring

Roll

Marked tip (actually ring)

Marked tip (actually tip)

INSTRUCCIONES DE OPERACIÓN

A.

 Toma de prueba RJ-45

B.

 Probar cable blindado

C.

 Indicador de batería baja

D.

 Botón de prueba o depuración

E.

 Selección de cables

F.

 Prueba de pares divididos

G.

  Tabla de cableado T56A o 

T56B

MODEL: Cable-Test™ Probador de cables 

TT64200

 

unidad principal

A

E

Remota

D

C
F

B

A

G

ADvERTENCIAS DE SEGuRIDAD

Este manual de instrucciones contiene advertencias y reglas 

de seguridad que el usuario debe observar para garantizar el 

funcionamiento seguro del instrumento y mantener su estado sin 

presentar peligro. Por lo tanto, lea estas instrucciones operativas antes 

de usar el instrumento.

!

!

ADvERTENCIA – No SE DEBE uSAR EN CIRCuIToS 

ENERGIzADoS

ESpECIFICACIoNES DE loNGITuD DEl CABlE

• Largo mín. del cable para pruebas: 91.4 cm.

• Largo máx. del cable para pruebas: 182.8 m.

•  Largo máximo del cable plano para el ensamblaje de cables con el fin de 

conectar la unidad principal o remota a una toma de pared o panel de 

parche: 45.7 cm.

Nota:

 Aunque el TT64200 está equipado con tomas de enchufe modulares 

de 8 posiciones, también pueden probarse conectores más pequeños de 6 

posiciones y 4 posiciones. El usuario debe tener presente que el empleo de 

conectores pequeños reducirá la cantidad total de inserciones de la toma 

durante la vida útil del producto.

pARA pRuEBAS CABlES DE pARChE

1. Conecte la unidad principal a un extremo del cable a probar.

2. Conecte la unidad remota al enchufe del extremo alejado del cable.

3. Pulse el botón TEST (prueba) para realizar la prueba.

4.  Lea las luces indicadoras (LED) para determinar el estado del 

cableado.

Nota: El probador se apaga automáticamente en 12 segundos.

pARA pRuEBAS CABlES INSTAlADoS  

1.  Usando el cable puente conecte la unidad remota a la toma de 

pared o puerto de panel de parche a probar.

2.  Usando el segundo cable puente conecte la unidad principal a la 

otra toma de pared o puerto de panel de parche a probar. 

3. Pulse el botón TEST (prueba) para realizar la prueba.

4.  Lea las luces indicadoras (LED) de estado para determinar cómo está 

el cableado.

Nota: El probador se apaga automáticamente en 12 segundos.
RESulTADoS DE pRuEBA

Indicadores de que PASA la prueba

10 Base-T

Token Ring

Blindaje

Cable de cruce

Dos luces 

indicadoras 

verdes (LED)  

en pares 

1-2 y 3-6. 

Ambos pares 

terminados 

correctamente

Dos luces 

indicadoras 

verdes (LED) 

en pares 

3-6 y 4-5. 

Ambos pares 

terminados 

correctamente

La luz indicadora 

verde (LED) SHIELD 

(blindaje) indica 

que el blindaje 

del cable está 

cableado correcta 

y continuamente 

a través de la 

terminación del 

enchufe modular.

Cuatro luces verdes 

indicadoras (LED) 

en pares 1-2, 3-6, 

4-5 y 7-8. 

Los cuatro 

pares tienen 

terminaciones 

correctas.

INDICADoRES DE FAllA

Una luz indicadora (LED) destellante indica que este par de 

cables tiene una falla. Una luz indicadora destellante en la sección 

FAIL (FALLA) indica la avería que se detectó. Si hay varias luces 

indicadoras destellantes quiere decir que hay varios pares y/o fallas 

diversas. Lo mejor es corregir las fallas de cables hasta que se 

verifique que los cables están correctos con las luces indicadoras 

verdes (LED) adecuadas.

•  

ABIERTo –

 No hay indicación de luz indicadora de "OPEN" (abierto). 

Un cable típico puede tener 2, 3 ó 4 pares. Los ABIERTOS aparecen 

con una luz indicadora (LED) apagada. El usuario determinará si 

hay un par presente y continuo o ABIERTO al comparar las luces 

indicadoras (LED) iluminadas con el número previsto de pares que 

deben estar buenos. Por ejemplo, al probar un cable de 4 pares, 

tres luces indicadoras iluminadas en el área PASS (PASA) indican la 

presencia de una condición ABIERTA en uno de los pares.

• 

CoRToCIRCuITo –

 Existe un cortocircuito.

•  

CABlEADo INCoRRECTo –

 Indica la asignación indebida de pares de 

cables individuales a patillas para los esquemas de cableado probados. El 

probador revisa configuraciones T568A, T568B, 10Base-T y Token Ring.

Reviews: