IM-P481-04
CTLS Issue 4
22
start of text under grey section header box
start of text continuing from previous page
TRANSLATION RUN OVER
TVA not installed and local set point selected
If the Spirax Sarco EasiHeat
TM
unit is not fitted with a TVA flowmeter then the system configuration is now
complete and the continue navigation button at the right-base of the screen can be used to navigate to next
page which is the Start Page (Figure 13, page 16 - Blue hand).
TVA installed and remote set point selected
On TVA flowmeter selection a data entry point shall be displayed in order for effective scaling of the
flowmeter (full engineering range for the 4-20 mA signal input to the Spirax Sarco EasiHeat
TM
system).
The full range values entered at this point should match exactly those that are programmed in the
TVA flowmeter parameters (Refer to Sections 4.2 and 4.2.1 for TVA commissioning data) as well as
remote set point.
Fig. 31
Fig. 32