When the anti-legionella button is pressed a confi rmation screen will appear, only if Independent High Limit
is fi tted (IHL). Ensure the boost cycle temperature is below the high limit set-point.
Anti-legionella
To minimise the growth of legionella bacteria from growing in the water pipeline a routine has been
programmed into the EasiHeat
TM
control system. The anti-legionella control and set-point page is accessible
from a button located on the main screen.
There are two modes of operation for the anti-legionella cycle that are selectable from the HMI pop up
screen, these are:
-
Manual
-
Automatic (timed)
Warning:
The temperature set-point during this cycle will exceed normal operating temperatures and could
cause scalding if water is used during the cycle. The cycle should only be initiated when it is safe to do so.
There must also be water drained from the circuit at the end of the cycle to assist in reducing the water
temperature.