background image

IM-P145-02 

 ST Issue 2

4

1.2 Access

Ensure safe access and if necessary a safe working platform (suitably guarded) 
before attempting to work on the product. Arrange suitable lifting gear if required.

1.3 Lighting

Ensure adequate lighting, particularly where detailed or intricate work is required.

1.4  Hazardous liquids or gases in the pipeline

Consider what is in the pipeline or what may have been in the pipeline at some 
previous time. Consider: flammable materials, substances hazardous to health, 
extremes   of   temperature.

1.5  Hazardous environment around the product

Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, 
extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive 
noise, moving machinery.

1.6  The system

Consider the effect on the complete system of the work proposed. Will any proposed 
action (e.g. closing isolation valves, electrical isolation) put any other part of the 
system or any personnel at risk? 
Dangers might include isolation of vents or protective devices or the rendering 
ineffective of controls or alarms. Ensure isolation valves are turned on and off in a 
gradual   way   to   avoid   system   shocks.

1.7  Pressure systems 

Ensure that any pressure is isolated and safely vented to atmospheric pressure. 
Consider double isolation (double block and bleed) and the locking or labelling of 
closed valves. Do not assume that the system has depressurised even when the 
pressure   gauge   indicates    zero.

1.8 Temperature

Allow time for temperature to normalise after isolation to avoid the danger of burns and 

consider whether protective clothing (including safety glasses) is required.

Viton 'O' ring:

If  the  Viton  'O'  ring  has  been  subjected  to  a  temperature  approaching  315°C  (599°F) 

or higher, it may have decomposed and formed hydrofluoric acid. Avoid skin contact 

and  inhalation  of  any  fumes  as  the  acid  will  cause  deep  skin  burns  and  damage  the 

respiratory system.

1.9  Tools and consumables

Before starting work ensure that you have suitable tools and /or consumables 
available. Use only genuine Spirax Sarco replacement parts.

1.10  Protective clothing

Consider whether you and / or others in the vicinity require any protective clothing 
to protect against the hazards of, for example, chemicals, high / low temperature, 
radiation, noise, falling objects, and dangers to eyes  and  face.

Summary of Contents for FTS14

Page 1: ...duct information 3 Installation 4 Commissioning 5 Operation 6 Maintenance 7 Spare parts Copyright 2014 Printed in GB FTS14 Austenitic Stainless Steel Ball Float Steam Trap DN15 to 1 DN25 Installation and Maintenance Instructions IM P145 02 ST Issue 2 1452050 2 ...

Page 2: ...IM P145 02 ST Issue 2 2 ...

Page 3: ... or condensate which is in Group 2 of the above mentioned Pressure Equipment Directive The products use on other fluids may be possible but if this is contemplated Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered ii Check material suitability pressure and temperature and their maximum and minimum values If the maximum operating limits ...

Page 4: ...trols or alarms Ensure isolation valves are turned on and off in a gradual way to avoid system shocks 1 7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure Consider double isolation double block and bleed and the locking or labelling of closed valves Do not assume that the system has depressurised even when the pressure gauge indicates zero 1 8 Tempera...

Page 5: ...ature of the product may reach temperatures in excess of 400 C 752 F Many products are not self draining Take due care when dismantling or removing the product from an installation refer to Maintenance instructions 1 14 Freezing Provision must be made to protect products which are not self draining against frost damage in environments where they may be exposed to temperatures below freezing point ...

Page 6: ... down configurations Standards This product fully complies with the requirements of the European Pressure Equipment Directive 97 23 EC Certification This product is available with certification to EN 10204 3 1 Note All certification inspection requirements must be stated at the time of order placement Optional extras FTS14X is available with an integral strainer screen to protect the internals fro...

Page 7: ...bar g 437 F 275 5 psi g Minimum operating temperature 0 C 32 F Note For lower operating temperatures consult Spirax Sarco Maximum FTS14 4 5 4 5 bar 65 psi PMX differential FTS14 10 10 bar 145 psi pressure FTS14 14 14 bar 203 psi Designed for a maximum cold hydraulic test pressure of 37 5 bar g 544 psi g 2 4 Materials Part Material Body and cover Austenitic stainless steel 316 EN 10213 4 1 4408 AST...

Page 8: ... Although the standard flow configuration is right to left R L the connection orientation can be changed on site by undoing the four cover bolts and moving the cover to the preferred flow orientation Note A new gasket must always be fitted Warning The cover gasket contains a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully 3 7 Traps should ...

Page 9: ...nternals 3 11 Float traps should be fitted as close as possible to the outlet of the plant to be drained otherwise the trap can steam lock Steam locking occurs when the pipe between the condensate outlet and the steam trap fills with steam preventing the condensate from reaching the trap This can lead to system waterlogging which will affect plant efficiency It is very similar to the air locking e...

Page 10: ...to the DN25 1 traps only Refit the pivot frame 12 by tightening the assembly set screws 7 to the recommended torque see Table 1 Replace float assembly 8 and pivot pin 14 Fit a new O ring 15 onto the body ensuring that the O ring contact surfaces are all clean and in good condition Care must be taken to ensure that the O ring is not damaged during assembly A suitable lubricant may be used to ease a...

Page 11: ... line are not supplied as spares Available spares Maintenance kit 3 5 6 2 off 7 2 off 8 9 12 14 16 1 only 18 Gasket set packet of 3 3 15 How to order spares Always order spares by using the description given in the column headed Available spares and state the size type of trap and pressure range i e 4 5 10 or 14 bar Example 1 Maintenance kit for a Spirax Sarco FTS14 4 5 steam trap 7 Spare parts 16...

Page 12: ...IM P145 02 ST Issue 2 12 ...