The TVA flowmeter normally
only requires a minimum of 6
pipe diameters upstream and
3 downstream of clear straight
pipe. These dimensions
assume a measurement
from a single 90
°
bend (see
Figure 11).
If any of the following configurations are present upstream of the TVA flowmeter:
-
Two right angled bends in two planes.
-
Pressure reducing valve.
-
Partly open valve.
Then it is recommended that the minimum upstream clear pipework is doubled to 12 diameters
(See Figure 12).
3D Minimum
6D Minimum
3D Minimum
6D Minimum
3D Minimum
12D Minimum
Note:
The 'U' syphon
and pressure sensor
must be used for
superheated steam
applications.
Note:
The ' U ' syphon and
pressure sensor must be used for
superheated steam applications.