4.2 Commissioning mode
The commissioning mode is used to zero the flowmeter, re-range, enable the pressure sensor
(for superheat applications), set and test the outputs and change the pass code.
All data entry is performed via a menu and sub menu configuration with the key pad buttons
used for navigation, i.e. to go deeper into the menu the right hand key is pressed, to scroll
up and down the menu the up and down keys are pressed and to exit from a sub-menu the
left key is pressed. Any data is entered using the OK button. The previously entered selection
will flash. After a period of five minutes without any keys being pressed the TVA flowmeter
will automatically default to the run mode.
For a full commissioning flow chart see Section 4.3.
To enter the commissioning mode press and hold down the 'OK' key for 3 seconds. The
display then shows:
Followed by:
The leading digit will flash indicating that this is the position of the cursor.
The default factory set pass code is 7452. (This can be changed from within the commissioning
mode). The pass code can be entered by using the up and down keys to increment the flashing
value and the left and right keys to move the cursor. Pressing 'OK' will enter the pass code.
If an incorrect pass code is used the display will automatically return to the run mode.
After the correct pass code is entered the display shows:
7452