IM-P192-02
MI Issue 2
40
4.9 ALARM sub-menu
This sub-menu gives access to setting the action that is required on the 4-20 mA output when
an error is detected by the TVA flowmeter electronics. It also gives access to the power alarm
function.
LOW
OFF
HIGH
ALARM
O/P
ALARM
POWER
ALARM
OFF
ON
4.9.1 O / P ALARM
HIGH
If the self-diagnostic electronics determine that the sensor output has been
constant for a period of time, or is not giving out a signal, it will set the 4-20 mA
output to 22 mA.
LOW
If the self-diagnostic electronics determine that the sensor output has been
constant for a period of time, or is not giving out a signal, it will set the 4-20 mA
output to 3.8 mA.
OFF
This disables the 4-20 mA alarm function.
4.9.2 POWER ALARM
OFF
This disables the power alarm function.
ON
This enables the power alarm function.
NO
yES
CONSt
ALARM
OFF
ON
SAt
ALARM
dELAy
XX