4-130
Flow-X─ Function Reference
Flow-X General functions - fxAPI_Table6_1952
fxAPI_Table6_1952
°API (60°F, 0 psig) --> CTL
This function calculates the volume correction factor for temperature from the API gravity value at 60°F
and the observed temperature according to API 1952 Table 6.
Compliance
ASTM-IP Petroleum Measurement Tables, American Edition, United States Units of
Measurement, 1952
Boundaries
Table 6 contains values for the following range:
Input value
Normal Range
EU
API Gravity at 60 °F
0 .. 100
°API
Observed temperature
0 .. 300
°F
Note that the table does not cover the full range, e.g. for an API gravity of 70 the table only specifies
values between 0 .. 150 °F
Function inputs and outputs
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name, tag
description and tag group
API at 60 °F
API gravity at 60°F and the
equilibrium pressure
°API
-20..120
0
Observed
temperature
°F
-100..400
60
Function
outputs
Remark
EU
SW tag
Alarm
Fallbac
k
Status
0: Normal
1: Input argument out of range
2: Calculation error
-
STS
FIOOR
CALC
1
CTL
Volume correction factor for temperature.
-
CTL
1
Calculation
out of range
With respect to the standard the input
values are:
0: In Range
1: Out of Range
-
OOR
0
Calculations
The table values are the standard, so no calculations are involved. The function performs an
interpolation between the table values that correspond to the input values.
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...