4-152
Flow-X─ Function Reference
Flow-X General functions - fxAPI_Table53E
fxAPI_Table53E
Description
Density (T) --> Density (15°C)
This function converts the density value at the observed temperature to the corresponding density at
15°C.
The temperature correction is according to API MPMS 11.2.4:2007 (GPA TP-27).
Compliance
API MPMS 11.2.4: Temperature Correction for the Volume of NGL and LPG Tables 23E, 24E,
53E, 54E, 59E & 60E, September 2007
GPA TP-27: Temperature Correction for the Volume of NGL and LPG Tables 23E, 24E, 53E,
54E, 59E & 60E, September 2007
Function inputs
Remark
EU
SW
tag
Range
Default
Name
Optional tag name, tag description
and tag group
Observed
density
Density at the observed
temperature
kg/m3
0..750
0
Observed
temperature
Temperature at which the relative
density is observed
°C
-100..150
15
API rounding
0: Disabled
The calculations are performed
with full precision and the
output values are not rounded
1: Enabled
The input and output values
are rounded as defined in the
standard
0
Function
outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Input argument out of range
2: Calculation error
3: No convergence
-
STS
FIOOR
CALCERR
NOCONV
Density at
15°C
DENS15
CTL
Volume correction factor for
temperature.
-
CTL
1
Calculation out
of range
With respect to the standard the input
values are:
0: In Range
1: Out of Range
-
OOR
0
Calculations
The calculations are in either full or partial compliance with the standard, depending on the selected
type of API rounding.
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...