Flow-X─ Function Reference
4-157
Flow-X General functions - fxAPI_Table54_2004
Function
outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Input argument out of range
2: Calculation error
3: No convergence
STS
FIOOR
CALCERR
Observed
density
Density at the observed
temperature and pressure
-
DENS
0
CTL
Volume correction factor for
temperature.
Value will be rounded according
to input 'API rounding'
-
CTL
1
CPL
Volume correction factor for
pressure
Value will be rounded according
to input 'API rounding'
-
CPL
1
CTPL
Combined volume correction
factor
CTPL = CTL * CPL
-
CTPL
1
K0
Actual value of constant K0 used
for CTL calculation
-
K0
0
K1
Actual value of constant K1 used
for CTL calculation
-
K1
0
K2
Actual value of constant K2 used
for CTL calculation
-
K2
0
Alpha
Thermal expansion factor at 60
°
F
!
1/°F
ALPHA
0
F
Compressibility factor
1/bar
F
0
Product
When input 'Product' is 'B - Auto
select', then the output is set to
the actual selected product of
table B (enumerative value as
defined for input 'Product'), else
the output is set equal to input
'Product'.
-
PRDCUR
0
Calculation out
of range
With respect to the standard the
input values are:
0: In Range
1: Out of Range
-
OOR
0
Calculations
The calculations are in either full or partial compliance with the standard, depending on whether API
rounding is enabled or not.
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...