4-194
Flow-X─ Function Reference
Flow-X General functions - fxGPA_TP15
Function inputs
Remark
EU
Range
Default
Name
Optional tag name, tag description and tag
group
Relative density at
60°F
-
0.3 .. 0.75
0
Observed
Temperature
°F
-100..200
60
API rounding
0: Disabled
Full precision (no rounding applied)
1: Enabled
Rounding as defined in ' GPA TP15:1988
/ API MPMS 11.2.2 Addendum':1994
-
0
P100 Correlation
0: Disabled
The standard correlation is commonly
used for pure products such as propane,
butane and natural gasoline. It only
requires the relative density and the
temperature to calculate the vapor
pressure
1: Enabled
The improved correlation requires the
vapor pressure at 100°F (37.8 °C). This
method is better suited for varied NGL
mixes Where different product mixes
could have the same specific gravity but
different equilibrium pressures.
-
0
Vapor pressure at
100°F
psia
0..500
0
Function outputs
Remark
EU
Fallback
Status
0: Normal
1: Input argument out of range
2: Calculation error
Vapor pressure
Vapor pressure at 60°F
psia
0
Range
With respect to the 2007 standard the combination of
relative density and temperature is:
0: In Range
1: Out of Range
-
0
Calculations
The calculations are in either full or partial compliance with the standards, depending on the selected
type of API rounding.
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...