4-220
Flow-X─ Function Reference
Flow-X General functions - fxISO5167_LongRadiusNozzle
pressure at the downstream
tapping (p
2
).
Temperature Location
1: Upstream
Input 'Temperature' represents
the upstream temperature (t
1
).
2: Downstream
Input 'Temperature represents
the temperature at the
downstream tapping (t
2
).
3: Recovered
Input 'Temperature' represents
the downstream temperature at
a location Where the pressure
has fully recovered (t
3
).
Since temperature measurement
is usually downstream of the
flow device this is the most
common setting.
-
2
Temperature Correction
This parameter specifies how the
temperature should be corrected
from downstream to upstream
conditions (or vice versa)
1: (1-
)/
Isentropic expansion using (1-
)/
as the temperature referral
exponent
2: Constant
Isentropic expansion using input
'Temperature Exponent' as the
temperature referral exponent [-
].
Please note that this value must
be < 0
3: Joule Thomson
Isenthalpic expansion using input
'Temperature Exponent' as the
Joule Thomson coefficient
[°C/bar].
This method is prescribed by
ISO5167-1:2003.
3
Temperature Exponent
Refer to input Temperature
Correction
Unit depends on input Temperature
Correction value
-
-
°C/bar
0
Density Location
This parameter specifies if and how
the density should be corrected from
downstream to upstream conditions
(or vice versa).
1: Upstream
Input 'Density' represents the
density at the upstream pressure
tapping (
1
).
2: Downstream
Input 'Density' represents the
density at the downstream
tapping (
2
).
3: Recovered
Input 'Density' represents the
density downstream at a
-
1
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...