Flow-X─ Function Reference
4-239
Flow-X General functions - fxISO6976_1995_M
Function outputs
Remark
EU
Fallback
Status
0: Normal
1: Input argument out of range
2: Calculation error
3: Mole fractions do not add up to 1.0 +- 0.0001
Superior calorific
value
Real superior calorific value on volume basis at
the reference conditions of temperature and
pressure
MJ/m3
0
Density
At the reference conditions of temperature and
pressure
kg/m3
0
Compressibility
-
1
Relative density
-
0
Molar mass
kg/kmol
0
Superior calorific
value
Real superior calorific value on mass basis at the
reference conditions of temperature and pressure
MJ/kg
0
Superior calorific
value
Real superior calorific value on mole basis at the
reference conditions of temperature and pressure
MJ/kmol
0
Inferior calorific value
Real inferior calorific value on volume basis at the
reference conditions of temperature and pressure
MJ/m3
0
Inferior calorific value
Real inferior calorific value on mass basis at the
reference conditions of temperature and pressure
MJ/kg
0
Inferior calorific value
Real superior calorific value on mole basis at the
reference conditions of temperature and pressure
MJ/kmol
0
Wobbe index
MJ/m3
0
Data range
With respect to the ISO6976-1995 standard the
combination of input values is:
0: In Range
1: Out of Range
-
Calculations
Calculations are performed in accordance with the standard.
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...