Flow-X─ Function Reference
4-281
Flow-X General functions - fxSolartron_Gas_C
fxSolartron_Gas_C
Description
The function calculates the density from a frequency input signal provided by a Solartron 7810, 7811 or
7812 gas densitometer and corrects it for temperature and velocity of sound effects in US customary
units.
The function requires that the calibration constants are based on the following units:
Temperature
°
F
Pressure
psi
Density
g/cc
Compliance
The calculations are in accordance with documents:
78125010 'Solartron 7812 Gas Density Transducer Manual', 2001.
78125040 Rev. C, 'Micro Motion 7812 Gas Density Meter', October 2007.
Function inputs
Remark
EU
SW tag
Range
Default
Name
Optional tag name, tag
description and tag group
Periodic time
In microseconds
Equals 1000 divided by the
frequency in [Hz]
s
0..1e6
0
Line temperature
Used when temperature
correction is enabled
°F
-
459.67..+1000
20
Temperature
correction
0: Disabled
1: Enabled
-
TEMPCOR
1
VOS correction
0: Disabled
1: Enabled
-
VOSCOR
1
Reference
temperature
Used when temperature
correction is enabled
°F
REFTEMP
0..200
60
K0
Constant K0 from calibration
certificate
-
K0
-1e9..1e9
K1
Constant K1 from calibration
certificate
-
K1
-1e9..1e9
K2
Constant K2 from calibration
certificate
-
K2
-1e9..1e9
K18
Constant K18 from calibration
certificate
-
K18
-1e9..1e9
K19
Constant K19 from calibration
certificate
-
K19
-1e9..1e9
K3
Constant K3 from calibration
certificate
-
K3
-1e9..1e9
K4
Constant K4 from calibration
certificate
-
K4
-1e9..1e9
Calibration gas
constant
Constant Kc from calibration
certificate
-
KC
-1e9..1e9
G value method
Method of determining value
G, which is the ratio of Gas
Specific Gravity and the Ratio of
Specific Heats
1: Use input 'G value'
2: Uses ratio of inputs
Uses the ratio of inputs
'Specific Gravity' and
'Ratio of Specific Heats'
-
GMETHOD
1
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...