4-288
Flow-X─ Function Reference
Flow-X General functions - fxSolartron_Liquid _C
'Based on Kr / Kj Constants'.
Constant needs to be obtained from
Solartron
Kj
Used when VOS method is set to
'Based on Kr / Kj Constants'.
Constant needs to be obtained from
Solartron
lbm/ft3
Liquid VOS
Velocity of sound of liquid
Used when VOS method is set to '
Based on VOS value'
ft/s
Function outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Input argument out of range
2: Calculation error
STS
FIOOR
CALCERR
Corrected
density
Density corrected for
temperature, pressure and VOS
lbm/ft3
CORDENS
0
Density
corrected for
temperature
lbm/ft3
TCORDENS
0
Density
corrected for
temperature and
pressure
lbm/ft3
PTCORDENS
0
Uncorrected
density
lbm/ft3
UNCDENS
0
Calculations
Density calculations are performed in g/cc and m/s, while the function inputs and outputs are in
lbm/ft3 and ft/s
The indicated density ρ
i
is calculated by
2
2
1
0
K
K
K
i
Where:
ρ
i
The indicated density
g/cc
K0
Obtained from the calibration certificate
-
K1
Obtained from the calibration certificate
-
K2
Obtained from the calibration certificate
-
τ
The time period in µS
s
The temperature corrected density ρt is calculated by
R
R
i
t
t
t
K
t
t
K
19
18
1
Where:
ρ
t
The density corrected for temperature
g/cc
K18
Obtained from the calibration certificate
-
K19
Obtained from the calibration certificate
-
t
The line temperature
°F
t
R
The reference temperature
°F
The pressure and temperature corrected density ρ
PT
is calculated by
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...