Flow-X─ Function Reference
4-291
Flow-X General functions - fxSolartron_Liquid_M
certificate
K21A
Constant from calibration
certificate
-
-1e9..1e9
-4.467e-1
K21B
Constant from calibration
certificate
-
-1e9..1e9
-8.633e-3
Kr
Used when VOS method is set
to 'Based on Kr / Kj Constants'.
Constant needs to be obtained
from Solartron
-
-1..+1
0.0
Kj
Used when VOS method is set
to 'Based on Kr / Kj Constants'.
Constant needs to be obtained
from Solartron
kg/m3
0..2000
0.0
Liquid VOS
Velocity of sound of liquid
Used when VOS method is set
to ' Based on VOS value'
m/s
0..2000
0.0
Function outputs
Remark
EU
SW tag
Alarm
Fallback
Status
0: Normal
1: Input argument out of
range
2: Calculation error
STS
FIOOR
CALCERR
Corrected density
Density corrected for
temperature, pressure
and VOS (provided that
particular correction is
enabled)
kg/m3
CORDENS
0
Density corrected for
temperature
kg/m3
TCORDENS
0
Density corrected for
temperature and
pressure
kg/m3
PTCORDENS
0
Uncorrected density
kg/m3
UNCDENS
0
Calculations
The indicated density ρ
i
is calculated by
2
2
1
0
K
K
K
i
Where:
ρ
i
The indicated density
kg/m3
K0
Obtained from the calibration certificate
-
K1
Obtained from the calibration certificate
-
K2
Obtained from the calibration certificate
-
τ
The time period in µS
s
The temperature corrected density ρt is calculated by
R
R
i
t
t
t
K
t
t
K
19
18
1
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...
Page 331: ...Flow X Function Reference 5 331 Flow X IO Functions fxPT100Table...
Page 349: ...Flow X Function Reference 6 349 This page is intentionally left blank for user notes...
Page 350: ...6 350 Flow X Function Reference This page is intentionally left blank for user notes...