4-308
Flow-X─ Function Reference
Flow-X General functions - fxVCone_C
Pressure Location 1: Upstream
Input 'Pressure' represents the pressure
at the upstream pressure tapping (p
1
).
Since the absolute pressure is usually
measured at the upstream tapping this
is the most common setting.
2: Downstream
Input 'Pressure' represents the pressure
at the downstream tapping (p
2
).
-
1
Temperature
Location
1: Upstream
Input 'Temperature' represents the
upstream temperature (t
1
).
2: Downstream
Input 'Temperature represents the
temperature at the downstream
tapping (t
2
).
3: Recovered
Input 'Temperature' represents the
downstream temperature at a location
Where the pressure has fully recovered
(t
3
).
Since temperature measurement is
usually downstream of the flow device
this is the most common setting.
-
2
Temperature
Correction
This parameter specifies if and how the
temperature should be corrected from
downstream to upstream conditions (or vice
versa)
1: (1-
)/
Isentropic expansion using (1-
)/
as
the temperature referral exponent
2: Constant
Isentropic expansion using input
'Temperature Exponent' as the
temperature referral exponent [-]
3: Joule Thomson
Isenthalpic expansion using input
'Temperature Exponent' as the Joule
Thomson coefficient [°F/psi].
This method is prescribed by ISO5167-
1:2003.
1
Temperature
Exponent
Refer to input Temperature Correction
Unit depends on input Temperature
Correction value
-
-
°F/psi
0
Density Location
This parameter specifies if and how the
density should be corrected from
downstream to upstream conditions (or vice
versa).
1: Upstream
Input 'Density' represents the density at
the upstream pressure tapping (
1
).
2: Downstream
Input 'Density' represents the density at
the downstream tapping (
2
).
3: Recovered
Input 'Density' represents the density
downstream at a location Where the
pressure has fully recovered (
3
).
-
1
Summary of Contents for flow-x
Page 1: ...Function Reference Certified flow calculations Flow and batch calculations Worksheet functions...