background image

Head Pressure Control Valves

OROA-5, ORI-6-65/225H, ORI-10-65/225-H, ORD-4

INSTALLATION INSTRUCTIONS

To ensure proper performance, head pressure control valves 

must be selected and applied correctly. This is covered thor-

oughly in Bulletin 90-30. However, proper installation proce-

dures are equally important.

VALVE LOCATION/PIPING SUGGESTIONS —

 The 

OROA, ORI and ORD valves can be installed in horizontal 

or vertical lines – whichever best suits the application, and 

permits easy accessibility of all valves. Consideration should 

be given to locating these valves so they do not act as an oil 

trap and so solder cannot run into the internal parts during 

brazing. Precautions should also be taken to install the valves 

with the flow in the proper direction.

The ORI valve CANNOT be installed in the discharge 

line for any reason.

Figures 1 and 2 are piping schematics only to illustrate the 

general location of the OROA, ORI, and ORD valves in 

the system. Sporlan recommends that recognized piping 

references be consulted for assistance in piping procedures.  

Sporlan is not responsible for system design, or for misap-

plication of its products. If these valves are applied in any 

manner other than described in this bulletin, the Sporlan 

warranty is void.

In most cases, the valves are located at the condensing unit.  

When the condenser is remote from the compressor, the usual 

location is near the compressor. In all cases, it is important 

that some precautions be taken in mounting the valves. It is 

suggested that they be adequately supported to prevent exces-

sive stress on the connections. Discharge lines are a possible 

source of vibrations and gas pulsations, which may result in 

fatigue in tubing, fittings, and connections. The severity of 

discharge gas pulses differs with each system. On some appli-

cations it may be necessary to dampen the pulses to protect 

the ORD-4 internal parts. 

Pulsations are best handled by a 

good muffler placed as close to the compressor as possible.

Vibrations from moving parts of the compressor are best 

isolated by flexible loops or coils (discharge lines 1/2” or 

smaller), or flexible metal hoses for larger lines.

For best results, the hoses should be installed as close to 

the compressor shut-off valves as possible, and mounted 

horizontal and parallel to the crankshaft 

or

 vertically upward. 

The hoses should 

never

 be mounted horizontal 

and

 90° from 

the crankshaft. A rigid brace should be placed on the outlet 

end of the hose to prevent vibrations beyond the hose.

The inlet connections on the OROA-5, ORI-6 and ORI-10 

valves should be sized the same as the outlet of the condenser 

where possible. The ORD-4 is available with 5/8” ODF and 

7/8” ODF solder connections. On systems with discharge 

lines smaller than 5/8” OD, the bypass line can be the same 

size as the discharge line and the ORD-4 connections can be 

bushed down. If the system capacity is greater than any of 

the head pressure control valves ratings, these valves can be 

applied in parallel.

CAUTION:

 When the head pressure control valves are fac-

tory installed and capped for future hook-up in the field, any 

holding charge in the condensing unit and valve assembly 

should be bled off from 

all

 sides of the valves before remov-

ing the caps. This will prevent the caps from blowing off due 

to any trapped refrigerant.

VALVE STRAINERS –

 

Catch-All

®

 filter-driers – 

See·All

®

 moisture and liquid indicator —

 Just as with 

any refrigerant flow control device, the need for an inlet 

strainer is a function of system cleanliness and proper instal-

lation procedures. When the strainer is used with the ORI, 

the tubing is inserted in the valve connection until the tubing 

and strainer flange ring are up against the tubing stop, thus 

locking the strainer in place. See Figure 3. In order for the 

strainer to seat properly against the tubing stop of the OROA 

condenser connection, the strainer is inserted into the tubing. 

The tubing is then inserted into the valve connection, thus 

locking the strainer in place. See Figure 4.

© Copyright 2016 by Sporlan Division, Parker Hannifin, Washington, MO

FOR USE ON REFRIGERATION and/or AIR CONDITIONING SYSTEMS ONLY

Tubing Stop

Strainer

Valve Connection ORI

Tubing Stop

Tubing

Tubing

Strainer

Valve Connection OROA

Condenser

Compressor

Receiver

ORD-4

ORI

Condenser

Compressor

Receiver

OROA

Figure 1

Figure 2

Figure 3

Figure 4

INSTALLATION & SERVICE INSTRUCTIONS

SD-68-52016

Reviews: