background image

Doc. No. IN031

Rev. C

Page 13 of 19

2.5. Vent Line Installation

Use only 2”, 3” or 4” Schedule 40 PVC or equivalent pipe

for vent line. Follow all applicable AARST, EPA, and/or

State Standards for Radon or VOC venting.

1. Place the lid of the AIRaider

TM

on to the tank lining up the

clips with the clasps on the tank. Adjust clasps so that when

anchored to the clips the lid sits snugly on the tank gasket.

2. Connect vent line to AIRaider

TM

lid using the enclosed

rubber coupling (See Figure 8).

3. The vent line must be routed in a fashion that allows the

system to exhaust above the level of the roof (See Figure 9).

NOTE: When “Freeze Up” is possible, a minimum pipe diameter

of 3” is recommended (See Figure 10).

4. The vent line must be pitched back toward the system to

prevent condensation build up.

5. Cement all fi7ings to ensure no leakage will occur. Be certain

to use cement that is suitable for potable water applications.

6. Install weather cap on top of the vent line. This cap should

not restrict air flow and must prevent rain, snow and other

contaminants from entering the vent line.

Failure to install a proper vent line

may cause contamination of the

water, outgassing of contaminants

into the building, and/or limit

system performance.

* The Manufacturer has found that vent lines less than 250 equivalent

linear feet do not cause a decrease in contaminant removal percentages.

90° Bend = 15 Equiv. Linear Ft ; 45° Bend = 7 Equiv. Linear Ft.

Figure 10

Vent Line Installation

(3 inch)

Figure 8

Vent Line Connection

Figure 9

Vent Line Installation

(2 inch)

Summary of Contents for AIRaider

Page 1: ...Doc No IN031 Rev C Page 1 of 19 Installation Operation Manual 3 Saber Way Ward Hill MA 01835 All Residential and Small System Models Except EZ95...

Page 2: ...tem Check 3 RETESTING 4 MAINTENANCE 4 1 Six Month Service recommended 4 2 Annual Service required 5 TROUBLE SHOOTING LIMITED WARRANTY Figure 1 Typical System 433 321 Figure 2 Bypass Solenoid Assembly...

Page 3: ...Installation site requirements 3 Inspection of System components 4 Quali ed Technicians are necessary 5 Knowledge of all contaminants in the water 1 1 Safety Ma7ers Safety is the most important step...

Page 4: ...d Garden Hose Five Gallon Bucket A Stop Watch or Watch with a Second Hand Or A Water Flow Meter Household water use must be discontinued during the following ow rate test Mid Range Flow Rate Test 1 A7...

Page 5: ...tional Fire Protection Association s NFPA National Electrical Code Standard 70 current edition for all commercial and industrial work All wiring must be performed by a quali ed and licensed electricia...

Page 6: ...s of each step prior to beginning the actual installation 1 System Location 2 Readying the System for Installation 3 Plumbing Hook Up 4 Electrical Hook Up 5 Vent Line Installation 6 Remote Air Intake...

Page 7: ...air quality may be required 5 System must be level The system should not be located on a signi cant slope as this may impede system performance Place the system in the location acceptable to customer...

Page 8: ...031 Rev C Page 8 of 19 Figure 3 Diagram of Installed System sold separately PATENTED AERATION PROCESS UNTREATED WATER FROM WELL EXISTING TANK GRUNDFOS MQ3 45 TREATED WATER SUPPLY MOUNTING BRACKET AIRa...

Page 9: ...plied 5 Plumb water line to house into the bypass opening labelled Water Out See Figure 4 6 Install pressure gauge on jet pump assembly See Figure 5 7 Install 2 1 gallon pressure tank See Figure 5 8 M...

Page 10: ...ump Follow wiring instructions provided by the pump manufacturer Warning Never remove the Receptacle from the Jet Pump Power Cord without connecting the wires thus exposed to the jet pump inside the j...

Page 11: ...Doc No IN031 Rev C Page 11 of 19 Figure 6 AIRaiderTM 433 Wiring Diagram...

Page 12: ...Doc No IN031 Rev C Page 12 of 19 Figure 7 AIRaiderTM 321 Wiring Diagram...

Page 13: ...3 is recommended See Figure 10 4 The vent line must be pitched back toward the system to prevent condensation build up 5 Cement all 7ings to ensure no leakage will occur Be certain to use cement that...

Page 14: ...locate the Air Intake in the vicinity of vents from furnaces barbecue grills etc NOTE In Line Air Filters are available from the Manufacturer Figure 11 Air Intake Connection 2 7 System Start Up 1 Remo...

Page 15: ...r should also start running The water level must rise regardless of how many taps are open within the residence c While the tank is lling li6 the lower oat Water in ow should stop and the blower will...

Page 16: ...mended The following procedures should be followed to maintain the AIRaiderTM Check and or clean the blower air intake lter Check and or clean any lters or strainer installed on the inlet line to the...

Page 17: ...clean sediment from bo7om of aeration tank if necessary Clean if necessary tank and di users of all mineral build up Chlorinate tank and lines by pouring cup of chlorine into the rst aeration chamber...

Page 18: ...ess than the water ow entering the system Check solenoids for proper operation Replace if necessary Check oat switches oat for proper operation Replace if necessary Check sediment strainer and or lter...

Page 19: ...S FOR A PARTICULAR PURPOSE THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THERE IS NO WARRANTY OF MERCHANTABILITY ALL OTHER WARRANTIES EXPRESSED OR WRITTEN ARE NOT VALI...

Page 20: ...3 Saber Way P O Box 8244 Ward Hill MA 01835 Phone 800 355 0901 Fax 978 521 3964 E mail sales spruce com...

Reviews: