Marley
/
Sigma F Series
Cooling Tower
/
Engineering Data : Piping Plan 4
9
C
H
MOTOR
C
F
COLUMN AND
ANCHOR BOLT
TYP. SINGLE CELL
D
TYP. MULTICELL
CL
COLUMN AND
ANCHOR BOLT
CL
RISER AND HEADER
C L
TOWER
AND F
AN
C L
FAN
CL
FAN
CL
RISER
CL
H
E
G
FAN
FLANGE IS
3
/
4
"
THICK. BOLT
CIRCLE CONFORMS TO 125 LB.
ANSI SPECIFICATIONS
10
1
/
8
"
1
'
-7
"
BASE OF
TOWER COLUMNS
RISER
CL CL
C L
FACE OF
A
DIA. GALVANIZED FLANGE
F
FAN TOWER
CL
INLET RISER
CL
MOTOR
CONCRETE
BASIN OPTION
B
DIAMETER
CROSSOVER PIPE
STAINLESS
STEEL BASIN
OPTION
END ELEVATION
SIDE ELEVATION
NOTE
1
Use this bulletin for preliminary layouts only.
Obtain current
drawings from your Marley representative.
2 Pumping head contributed by the tower is static lift E. Actual
pumping head will vary according to tower circulating GPM. Total
pumping head will be furnished at time of proposal.
3 If your application requires a bypass system, recommended location
is through the tower endwall into the plenum area. Review of the
system by SPX engineering is required.
4 All header and riser piping to be furnished by others. A corrosion-
resistant material or coating for piping is recommended. Do not
support riser dead load or operating load from inlet connection or
tower structure.
PLAN