17
Basin heaters systems will not prevent the coil from freezing.
Unless some means of freeze prevention is incorporated into your
system, the tower basin and exposed pipework should be drained at
the beginning of each wintertime shutdown period.
If fluid cooler basin is drained, verify that all basin heaters have been
shut off either by automatic cutoff or disconnect switch.
Protection against Coil Freezing:
Ethylene and propylene glycol solutions are the best means to protect the
coil from freezing. The following table provides the coil volume for each
MC Fluid Cooler model. When the use of industrial antifreeze solutions is
not possible, the system must be operated to meet both of the following
conditions.
1. Maintain sufficient flow rate through the coil.
2. Maintain sufficient heat load on the process fluid. Fluid exiting the
coil must be maintained at or above 8°C. Cycling of the recirculation
pump should not be used to control process temperatures.
Draining the coil is not acceptable as a normal method of freeze
protection—draining promotes corrosion inside the coil tubes. Drain-
ing is acceptable in an emergency if the coil is not protected by an
antifreeze solution.
It is recommended that you discuss your freeze prevention options with
your local Marley sales representative.
Operation
Warning
Caution
Caution
Warning
Model
Coil Volume
liters
Model
Coil Volume
liters
MCF7012_081
42
MCF7055_081
265
MCF7012_101
49
MCF7055_101
333
MCF7012_121
61
MCF7055_121
401
MCF7013_081
64
MCF7073_081
163
MCF7013_101
79
MCF7073_101
204
MCF7013_121
95
MCF7073_121
246
MCF7014_081
87
MCF7074_081
231
MCF7014_101
106
MCF7074_101
288
MCF7014_121
129
MCF7074_121
344
MCF7054_081
174
MCF7075_081
337
MCF7054_101
220
MCF7075_101
424
MCF7054_121
261
MCF7075_121
507