20
centrations. The following table shows the minimum amount of blowdown
(percent of flow) required to maintain different concentrations with various
cooling ranges*:
* Range = Difference between hot water temperature and cold water temperature.
EXaMPLE:
EXaMPLE:
44.2 L/s circulating rate, 10°C cooling range. To
maintain 4 concentrations, the required blowdown is 0.458% or .00458
times 44.2 L/s, which is 0.2 L/s.
If fluid cooler is operated at 4 concentrations, circulating water will contain
four times as much dissolved solid as the makeup water, assuming none
of the solids form scale or are otherwise removed from the system.
When water treatment chemicals are added, they should not be in-
troduced into the circulating water system via the water collection
basin of the fluid cooler. Water velocities are lowest at that point,
which results in inadequate mixing. An ideal location would be the
distribution piping on the pressure side of the pump.
Note
Operation
Cooling Range
Number of Concentrations
1.5X
2.0X
2.5X
3.0X
4.0X
5.0X
6.0X
3°C
.78
.38
.25
.18
.11
.08
.06
6°C
1.58
.78
.51
.38
.25
.18
.14
9°C
2.38
1.18
.78
.58
.38
.28
.22
11°C
3.18
1.58
1.05
.78
.51
.38
.30
14°C
3.98
1.98
1.32
.98
.64
.48
.38
Multipliers are based on drift of 0.02% of the circulating water rate.