Marley
/
Sigma Steel
Cooling Tower
/
Engineering Data : Inlet Piping
9
C
C
COLUMN AND
ANCHOR BOLT
TYP. SINGLE CELL
D
TYP. MULTICELL
CL
COLUMN AND
ANCHOR BOLT
CL
FAN
CL
INLET
CL
INLET
CL
FAN
CL
F
MIN
REQUIRED CLEARANCE
C L
E
G
C OF FLANGE TO
BASE OF TOWER
COLUMNS (USE FOR
STATIC LIFT)
FAN
FACE OF
A
DIA
INLET FLANGE
MARLEY PIPING
STOPS HERE
B
DIA FLOW
CONTROL VALVE
CL
L
C L
TOWER
CL
NOTE
1
Use this bulletin for preliminary layouts only.
Obtain
current drawings from your Marley sales representative.
2 Pumping head contributed by the tower is static lift
“G”. Actual pumping head will vary according to tower
circulating GPM. Total pumping head will be furnished at
time of proposal.
3 If your application requires a bypass system,
recommended location is through tower endwall into
plenum area. Review of the system by SPX engineering is
required.
4 Marley piping terminates at face of a cast iron flat face
flange. Bolt circle conforms to class 125 lb. ANSI B 16.1
specifications.
5 Supports on tower for crossover piping are part of the
tower design.
Do not support the riser’s dead load or
operating load from the tower. Do not brace the riser’s
seismic or thrust loads against the tower.
6 Butterfly valves or piping expansion joints (if used) are
by others and must be located outside the limits of the
cooling tower “
F
”.
7 Motor must be located 180° from inlet.
Tower
Model
GPM
per cell
Dimensions
A
B
C
D
E
F
G
121-111
500-3800
10"
8"
6'-0"
12'0"
8'-10
1
⁄
2
"
13'-1
1
⁄
4
"
14'-6
3
⁄
4
"
3801-4500
12"
10"
9'-0
1
⁄
2
"
14'-7
3
⁄
4
"
122-111
650-6000
14"
10"
8'-0"
16'-0"
10'-0
1
⁄
2
"
14'-1
1
⁄
4
"
14'-7
3
⁄
4
"
123-111
650-6000
14"
10"
8'-0"
16'-0"
11'-0
1
⁄
2
"
15'-1
1
⁄
4
"
14'-7
3
⁄
4
"
124-111
1000-6000
14"
10"
10'-0"
20'-0"
11'-0
1
⁄
2
"
15'-1
1
⁄
4
"
14'-7
3
⁄
4
"
6001-7500
16"
12"
11'-1
1
⁄
2
"
14'-8
3
⁄
4
"
125-111
1000-7500
16"
12"
10'-0"
20'-0"
13'-1
1
⁄
2
"
17'-1
1
⁄
4
"
14'-8
3
⁄
4
"
126-111
1000-9000
16"
12"
12'-0"
24'-0"
13'-1
1
⁄
2
"
17'-1
1
⁄
4
"
14'-8
3
⁄
4
"
127-111
1500-10500
18"
14"
14'-0"
28'-0"
13'-5
5
⁄
8
"
17'-1
1
⁄
4
"
14'-9
3
⁄
4
"
Summary of Contents for Marley Sigma Marley Sigma Steel
Page 1: ...Marley Sigma Steel CoolingTower Engineering Data Specifications...
Page 2: ......