24
To remove the eliminators, place both hands on the eliminator face and push
up, this will indicate where one assembly stops and another starts. Push a
single section up until it hits the top of the metal retaining channel (1). Push
the bottom side of the pack down inside the fluid cooler (2). Turn the pack
sideways and remove the eliminator (3). Repeat this procedure for other
packs to gain necessary access. Proper eliminator pack replacement is
essential to operation. Incorrect installation may result in excessive drift rates
and fan inefficiency! To ensure packs are reinstalled in the correct orientation,
it is recommended that one pack is left in its original location inside the fluid
cooler as a reminder of pack orientation. Place packs in the fluid cooler in the
order they were removed. Packs should nest tightly with each other, leaving
a level surface with no gaps.
maintenance