background image

21

TROUBLESHOOTING GUIDE (MODELS 200-750)

SYMPTOM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

A)  Water downstream of dryer

1.  Residual free moisture remaining in 

downstream pipelines

2.  Air bypass system is open

3.  Inlet and Outlet connections are reversed

4.  Air lines downstream of dryer are exposed 

to temperatures below the dew point.

5.  Excessive free moisture (bulk liquid) at 

dryer inlet.

6.  Condensate not being drained  

7.  Dryer overloaded resulting in elevated 

dew point.

8.  Refrigeration system not functioning 

1.  Blow out system with dry air

2.  Check valve positions

3.  Check for correct connection

4.  Insulate or heat trace air lines exposed to 

low ambients or dry air to lower dew point

5.  Install separator ahead of dryer

6.  See C below

7.  See C below

8.  See C below

B)  High pressure drop across dryer

1.  Excessive air flow

2.  Freezing of moisture in evaporator 

because of refrigeration system fault

3.  Filter loaded with solid particulates 

1.  Check flow rate

2.  See C below

3.  Replace filter element

C)  Checkpoint faults

1.   Power on light off

2.  Compressor on light off 

 

3.  Alarm/Service alert light on 

-check Display for active 

conditions

SERVICE DRYER

  

LOW PRESSURE

  

HIGH PRESSURE

NOTE: If high refrigerant pressure 

occurs, switch must be manually 

reset  

 

  

HIGH TEMPERATURE

(also observed as high reading on 

temperature indicator)

  

DRAIN

 

COMPRESSOR

HEATER

TEMP SENSOR

a.  Power failure; open circuit 

a.  Compressor commanded off by manual 

switch or programmed schedule

b.  Open circuit

c.  Control circuit open on high or low 

pressure cutout

a.  Service interval specified has elapsed

a.  Hot gas bypass valve requires adjustment

b.  Low on refrigerant

a.  Lack of condenser cooling 

 

Air-cooled - Ambient temperature too 

high, clogged condenser fins, obstructed 

flow across condenser, faulty fan motor or 

fan control switch.

 

Water-cooled - Cooling temperature too 

high, flow too low, clogged strainer, faulty 

water regulating valve  

a.  Dryer overloaded

b.  Refrigeration system off or not cooling 

sufficiently

a.  Drain line restricted or frozen

b.  Drain mechanism faulty

a.  Faulty compressor contactor.

b.  Faulty N.O. auxiliary contact on 

compressor contactor.

a.  Faulty compressor contactor.

b.  Faulty N.C. auxiliary contact on 

compressor contactor.

a.  Temperature sensor or wiring to sensor 

is open (only the left-most LED in the 

temperature display will be illuminated).

b.  Temperature sensor or wiring to sensor is 

shorted (all of the LEDs in the temperature 

display will be illuminated).

a.  Check for power to dryer

a.  Check current command status

b.  Check power to compressor

c.  Check display for fault

a.  Perform scheduled service

a.  Contact qualified technician or 

manufacturer’s service department

 

Check air temperature 6” in front of 

condenser;  Clean condenser and check 

for free air flow; Check fan and switch 

operation

 

Check cooling medium temperature and 

flow, clean strainer, check valve operation

a.  Check compressed air flow, temperature, 

and pressure

b.  Check power to unit, power to 

compressor, Low or High pressure faults 

Have qualified technician evaluate system 

a.  Open drain line

b.  Turn 3-way valve to horizontal position 

and open petcock for manual draining. 

Rebuild drain mechanism.

a.  Check wiring and operation of contactor.

b.  Check wiring and operation of auxiliary 

contact.

a.  Check wiring and operation of contactor.

b.  Check wiring and operation of auxiliary 

contact.

a.  Replace sensor or repair wiring.

b.  Replace sensor or repair wiring.

NOTE:  After fault correction, press reset button to clear display

Summary of Contents for Hankison HPRP Series

Page 1: ...yers Models HPRP100 HPRP125 HPRP150 HPRP200 HPRP250 HPRP300 HPRP400 HPRP500 HPRP600 HPRP750 FOR M NO 5002730 R EVI S ION 01 2012 R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E...

Page 2: ...r purification Refer to applicable standards and specifications for the requirements for breathing quality air RECEIVING MOVING AND UNPACKING A RECEIVING This shipment has been thoroughly checked pack...

Page 3: ...operate in altitudes up to 4500 feet 1370 meters If dryer is installed in an altitude above this and has not been preset at the factory for this altitude contact manufacturer s Service Department F T...

Page 4: ...the dryer if an unusual noise is heard or if the discharge line does not get hot the refrigeration compressor may be running in the reverse direction Immediately stop the dryer reverse two of the powe...

Page 5: ...F 43 C Water cooled models 130 F 54 C E Minimum ambient temperature 40 F 4 C 2 2 Start up A Models 100 150 Energize compressor by positioning the on off switch in the on I position Compressor on ligh...

Page 6: ...p and Down arrow buttons to set minutes 00 10 20 30 40 50 not shown if hour setting is IGNORE Press Enter to accept new value and return to Day of week on off Repeat steps a through c as needed d Push...

Page 7: ...l NOTE Interface panel will scroll through three screens Current Time Operating Status Hours to Service and Total Operating Hours a Verify that current time is correct b Check HRS TO SERVICE this indi...

Page 8: ...ake up to two seconds as certain processing functions may require completion before serial port is acknowledged Dryer responds with line feed 0AH carriage return 0DH and character string 1 2 3 4 5 6 7...

Page 9: ...110 F 120 F psig kgf cm2 27 C 32 C 38 C 43 C 49 C 50 80 100 125 150 175 200 3 5 5 6 7 0 8 8 10 5 12 3 14 0 1 35 1 50 1 55 1 63 1 70 1 75 1 80 1 05 1 17 1 23 1 31 1 37 1 42 1 47 0 84 0 95 1 00 1 07 1...

Page 10: ...A 1 1 2 0 50 Hz N A 0 9 1 7 Electrical Data Nominal Voltage 115 1 60 208 230 3 60 Min Max Voltage 104 127 187 253 Input Power Rated Flow watts 932 1280 1298 1255 1962 Rated Load Amps 10 2 13 0 7 5 10...

Page 11: ...low Required with 85 F Cooling Water gallons per minute 60 Hz 2 0 2 1 4 9 6 8 50 Hz 1 7 1 8 4 1 5 6 Electrical Data Nominal Voltage 208 230 3 60 Min Max Voltage 187 253 Input Power Rated Flow watts 19...

Page 12: ...STUD L2 L1 L2 230 VAC CUSTOMER SUPPLIED L1 PE PILOT LIGHT POWER ON T2 T2 T2 T1 T1 A PE T2 T1 T1 FPS 1 FAN 1 MTR2 START RELAY SR SR L3 L3 M 6 5 S CAPACITOR 4 OVERLOAD 3 1 3 MTR1 COMPRESSOR R C S POWER...

Page 13: ...CONT 1 PE PE L1 CONT 1 6 L2 GROUND STUD L2 L1 PE 230 VAC CUSTOMER SUPPLIED L1 L2 L2 L2 L1 L2 L1 L1 T2 T2 T1 T1 CONT 1 L1 N 4 5 5 A PE 6 FAN 1 HARNESS HEATER HARNESS PE L2 T2 T1 FPS 1 H1 H2 HEATER 1 MT...

Page 14: ...00 PE TB1 L1 L2 L3 L1 L1 460 VAC 3 PHASE 60 Hz L1 L2 L3 L1 CONT 1 T1 PE TB2 T1 T2 T3 T3 T2 T3 TB2 PE T2 T3 T2 FAN 1 HARNESS FPS 1 MTR2 FAN 1 MTR1 T1 T1 T1 COMPRESSOR HARNESS TO SHEET 02 43 42 X 40 41...

Page 15: ...W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 00 Chassis Gnd TB2 X 24VAC IN 24VAC IN W3 W2 W1 X TB2 3 X REMOVE JUMPER IF OPTIONAL DRAIN INSTALLED 4NO TB2 TB2 TB2 TB2 TB2 19 20 21 18 17 19 20...

Page 16: ...VAC 3 PHASE 60 Hz TB1 L1 L3 L2 L1 CONT 1 T1 DISCONNECT SWITCH PE TB2 T1 T2 T3 T3 T2 T3 TB2 PE T2 T3 T2 FAN 1 HARNESS FPS 1 MTR2 FAN 1 MTR1 T1 T1 T1 COMPRESSOR HARNESS TO SHEET 02 43 42 X 40 41 39 38...

Page 17: ...put W27 W18 W17 W16 N A N A W25 W23 FROM SHEET 01 01 03 02 00 Chassis Gnd TB2 X 24VAC IN 24VAC IN W3 W2 W1 X TB2 3 X REMOVE JUMPER IF OPTIONAL DRAIN INSTALLED 4NO TB2 TB2 TB2 TB2 TB2 19 20 21 18 17 19...

Page 18: ...18 WIRING DIAGRAM Models 200 750 575 460 3 60 Transformer Pack...

Page 19: ...600 23 62 600 30 15 766 30 15 766 30 15 766 30 15 766 30 15 766 30 15 766 30 15 766 E 17 62 448 17 62 448 17 62 448 30 15 766 30 15 766 30 15 766 30 15 766 39 62 1006 39 62 1006 39 62 1006 F 19 62 49...

Page 20: ...emperature and pressure flow rate compressor capacity and ambient air or water temperature See D below B High pressure drop across dryer 1 Excessive air flow 2 Freezing of moisture in evaporator becau...

Page 21: ...of condenser cooling Air cooled Ambient temperature too high clogged condenser fins obstructed flow across condenser faulty fan motor or fan control switch Water cooled Cooling temperature too high f...

Page 22: ...5002016 Compressor Only 3221303 3232809 3221304 5002921 3227182 3210937 3211540 3210939 5002930 3232811 Fan Motor 3238932 3233153 3233153 5002922 3233153 3233152 3228005 3228005 5002931 3228005 Fan B...

Page 23: ...art THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRAN...

Page 24: ...ankisonintl com Improvements and research are continuous at Hankison an SPX Brand Specifications may change without notice ISSUED 01 2012 Form No 5002730 Revision A COPYRIGHT 2012 SPX Corporation HPRP...

Reviews: