background image

17

Change user profile / password

 

Procedure:

Click on User > User profile.

Change/Complete the input fields.

Confirm your input by clicking on 

Apply.

Click on User > Change password.

Enter the old password (Standard: 

admin).

Issue a new password.

Click on Apply in order to change 

the password.

Setting the date and time 

For correct local time, and winter/

summer time changeover, the rel

-

evant time zone must be set. The 
following values are pre-set in the 
as-delivered status of the Gateway:

 

• German timezone (UTC+01:00)

 

• Automatic summer time change

-

over deactivated  

• Automatic time setting (NTP 
server) activated

Procedure:

Click on Basic settings > Date / 

time.

Select your time zone.

Click on automatic summer time 

setting if your location changes over 

between summer and winter time.

Select how you wish the time 

setting to take place (automatically/
manually). Observe the information 

on time setting in the commissioning 

requirements.

Click on Apply to save your set

-

tings/changes.

You are automatically logged out 

of the Gateway.

Check/change the  
network settings 

Procedure:

Click on Basic settings > Network.

Check the network settings for 

correctness. Change the IP settings 

if other IP addresses are required or 

necessary.

To create a connection with the 

Internet, the Gateway requires 
valid network information. If this is 

entered incorrectly, no connection 

can be established with the time 

server in the Internet, or the Apple 

Push Notification Service for the 
Siedle app cannot be reached.

Check the settings you have car

-

ried out for correctness. Click on 

Apply to save any changes you have 

made.

Setting video memory/door call 

In the menu 

Basic settings > Video 

memory/Door call,

 you can carry 

out settings relating to the video 

memory and door call. Both setting 

ranges are visually separated by a 

frame.

Procedure:

Click on Basic settings > Video 

memory/door call.

Video memory settings

:

Activate the automatic video 

memory if you wish an image to 

be taken of the person calling after 

every door call.

Activate the manual video memory 

if you wish users of the Siedle app to 

be able to manually take additional 

images.

Set the time in seconds after 

which you wish an image to be 

automatically taken after a door call 

(standard setting: 5 seconds).

Enable automatic deletion of 

images to automatically delete 
images that have exceeded the set 

age (GDPR functionality).

For automatic deletion of images, 

set the maximum age of images in 

days.

Door call option settings:

Activate the direct door call if you 

wish users to be able to call door call 
stations directly.

Activate the camera observation if 

you wish users (except for the Siedle 
app) to be able to display a live pic-

ture from the respective accessible 

bus/IP camera.

Existing bus cameras can be selected 

directly.

IP cameras can be additionally 
integrated into the Siedle IP users 

(except for the Siedle App).

 This 

requires the bus cameras for the 
camera observation function to have 

been activated in the Gateway (SG: 

Basic settings> Video memory/door 

call >Activate camera observation).

 

With the Siedle IP users, you can 
select the bus cameras in the oper

-

ating menu.

If you install a storey call button in 

your building, this can be connected 

directly to the Gateway.

 

However, 

it is only possible to select a user 

(except for the Siedle App) for the 

storey call once you have created an 

IP user / IP group.

Video settings

 

The standard bus camera on the 
door supports the PAL colour trans

-

mission system.

If an NTSC camera is used on the 
door, then the camera mode must 

be changed in the Gateway’s basic 
settings.

Procedure:

Click on Basic settings > Video.

 

Activate NTSC camera mode.

Click on the “Apply” button.

Summary of Contents for SG 650-0

Page 1: ...SG 150 0 Commissioning instruction Smart Gateway ...

Page 2: ...er product 14 Downloading and installing the bus programming software 14 Commissioning Manual programming 15 Programming using the PC and bus programming software BPS 650 16 Performing a system update 16 Change user profile password 17 Setting the date and time 17 Check change the network settings 17 Setting video memory door call 17 Video settings 17 Creating IP users 18 Deleting IP users 18 Crea...

Page 3: ... Gateway in the In Home bus and exporting the configuration 10 Login on the Gateway 16 Performing a system update 16 Change user profile password 17 Setting the date and time 17 Check change the network settings 17 Setting video memory door call 17 Import In Home bus configuration 19 Creating IP users Creating IP groups 18 Storey call Defining IP users IP group 18 Registering IP users 18 Set up th...

Page 4: ... repair sale exchange uninstall the app from this device Never hand over an smartphone with an operable app to a third person Delete the affected IP user from the Gateway This ensures that the affected IP user no longer has access to the door station In case of emergency Pull the network cable out of the LAN connection of the Gateway or Deactivate the WLAN of the WLAN router Block any existing ext...

Page 5: ...xiom Overview BVNG 650 Siedle intercom system building installation Door station WLAN SG 150 Mobile phone with installed Siedle app for Smart Gateway WLAN Internet SG 150 ERT ETb TbM S1 S1 E1 E1 PE PE TaM 0000000000000 Smart Gateway SG 150 0 IP 20 www siedle com Link In Home Status Reset Prog ERT ETb TbM S1 S1 E1 E1 PE PE TaM 0000000000000 Smart Gateway SG 150 0 IP 20 www siedle com Link In Home S...

Page 6: ...esses 25 Programming the In Home bus manually or using the bus programming software 10 Export the In Home bus configuration from the bus programming software 18 Import the In Home bus configuration 19 Install the software Siedle app on the terminals mobile phone and log in at the Gateway 19 22 Mobile network connection 21 Carry out a complete function test and hand over the documentation files to ...

Page 7: ...dual functions are not available for technical reasons Functions applicable across individual lines Door calls selective door dialling and switching and control functions can also be used across individual lines Internal speech communication and call forwarding between users is only possible within a line Connection of bus and IP address If you are operating the Siedle intercom and the Gateway in ...

Page 8: ...n entrance 2 Door call station Side entrance 2 Internal call station 1 1 Internal call station 2 1 Gateway 1 Sum 7 Max number of bus addresses per bus line 31 Additionally usable free bus addresses 24 The result A maximum of 25 bus addresses can be used in the Smart Gateway for the connec tion of IP users or IP groups 24 free bus addresses 1 already assigned bus address of the Smart Gateway System...

Page 9: ...e Change the password Basic settings Date time Network Video memory Door call Video Call number prefixes In Home bus Bus adresses Bus users Network user Licences IP users IP groups Telephony link Help Documentation Commissioning software Support System Protocols Safe Restore Update Reset Restarting Log out Preparation ...

Page 10: ...le at the Gateway When carrying out manual programming you can assign only one bus address to the Smart Gateway to allow either an IP user or an IP group to be selectively called If this is not ade quate you must carry out program ming using the bus programming software If you decide in favour of manual programming the steps with bus programming software are omitted Remarks on the Finder function ...

Page 11: ...ting network router wireless LAN router managed switch server The network setting of the Gateway is in the as delivered status DHCP client active The DHCP client is enabled on your commissioning Laptop PC to be able to request a network address from the DHCP server router wire less LAN router managed switch server Remarks In the delivery status the Gateway is delivered with an active DHCP client a...

Page 12: ... a different language 5 Enter the user name admin 6 Enter the relevant password standard admin 7 Click on Log in 8 The administrator user interface of the Gateway appears 9 Click on Basic settings Network 10 The network settings are dis played 11 Remove the tick under Obtain IP address automatically by DHCP 12 The network settings are now highlighted in white and can be changed 13 Execute the chan...

Page 13: ...te then the time must be reset after each power failure or reset as there is no buffer battery Alternatively you can operate the Gateway with manual time setting at an uninterruptible power supply Sufficient number of user licences For each IP user Siedle app etc one user licence is required There are 5 user licences contained in the scope of supply Other user licences can be ordered under www sie...

Page 14: ...require the MAC address hardware address of the Gateway e g 00 10 20 30 a1 b2 The MAC address of the Gateway can be found on the packaging on the device sticker and in the device information of the browser based user interface Procedure 1 Register your Gateway on the mysiedle service portal 2 Download existing system updates and save these on your commis sioning laptop Downloading and installing t...

Page 15: ...d down the light programming button for 4 seconds A protracted acknowl edgement tone is then audible which is repeated every 5 seconds as long as the programming mode remains active 1 Switch on the programming mode At the BNG BVNG 650 press the programming mode button briefly The LED 1 flashes in a 2 second rhythm to indicate that the program ming mode is active 4 On the door station press and hol...

Page 16: ...C before every system update The system update only affects the Gateway and the connected hard ware Update via local update tool Procedure 1 To access the latest software update please download the update tool from www siedle de sg 150 2 Save the file with the extension exe to your hard drive 3 Activate the installation process by double clicking and run the tool 4 Confirm any pop up queries about...

Page 17: ...eo memory and door call Both setting ranges are visually separated by a frame Procedure 1 Click on Basic settings Video memory door call Video memory settings 2 Activate the automatic video memory if you wish an image to be taken of the person calling after every door call 3 Activate the manual video memory if you wish users of the Siedle app to be able to manually take additional images 4 Set the...

Page 18: ...er 6 Select the IP users for the IP group by clicking on Add and confirming your selection with Close 7 Save the IP group by clicking on Save Storey call Defining IP users IP group The call button for the storey call is connected directly at the Gateway terminal ERT and ETb and is there fore independent from the rest of the In Home bus A door call via the storey call is processed directly in the G...

Page 19: ...t the Siedle App on your smartphone and log in using the login data QR code assigned in the Gateway For successful login both devices must be connected to the Internet Always use the latest version of the Siedle app Commission the Siedle app 1 Install the Siedle App on your Smartphone You can obtain the Siedle App from the App Store or Play Store 2 Create a new IP user Siedle App in the Smart Gate...

Page 20: ...C system if required 11 When logging in with SIP client enter the user authentication speci fied by the TC system if required 12 Select the supported DTMF mode 13 If required define a call number prefix 14 Click on the Apply button Commissioning Link Siedle Axiom Procedure 1 Create the Siedle Axiom in the Gateway as an IP user 2 Under Network users Telephony connection open the SIP client that you...

Page 21: ...Commission the Siedle app 6 Complete function check Sequence Install the mobile network connection ERT ETb TbM S1 S1 E1 E1 PE PE TaM 0000000000000 Smart Gateway SG 650 0 IP 20 www siedle com Link In Home Status Reset Prog Infographic Connecting a Mobile Terminal to a Smart Gateway Internet Router Siedle Server Mobile WLAN Door station Indoor station Siedle App Smart Gateway QR Code ...

Page 22: ...ection with static or dynamically changing public IP address Download The frame rate number of frames per second of the transmitted video stream from the Siedle Server to the Siedle App depends on the data transmission rate that is available for the mobile network connection at the time of the door call Bandwidth 2 MBit s approx 5 frames second are shown Bandwidth 4 MBit s approx 10 frames second ...

Page 23: ...Siedle app Mobile internet connec tion IPv4 connection Public IP static or dynamic Download see page 22 Upload constant 512 kBit s Stable WLAN or mobile phone connection 3G 4G 5G SIP VoIP enabled Provider Download constant at least 512 kBit s Upload see page 22 SIP VoIP enabled Public IP static or dynamic WLAN LAN In Home bus Infographic Mobile phone network requirements 3G 4G 5G ...

Page 24: ... Reset 2 Click on Restore as delivered status in order to reset the Gateway 3 In response to the confirmation prompt click on Yes if you wish to reset the Gateway Restarting the Gateway If the IP settings have been changed in the IP network with DHCP oper ation the Smart Gateway has to be restarted A restart corresponds to switching the power supply to the Smart Gateway off and on again After a re...

Page 25: ...line rectifier and end it after 2 seconds at the earliest 10 The reserved In Home bus address es has have been assigned to the Gateway and can be used for programming configuring the In Home bus 11 Repeat the steps for program ming with PC and Bus programming software BPS 650 Licenses User licences There are 5 user licences for IP users contained in the scope of supply For each IP user you wish to...

Page 26: ...system update Procedure 1 Click on System Protocols 2 Click the download icon to save the reqired log file Backing up Restoring the system In the Gateway you can back up and restore the configuration data the operating data or also both together After completion of the successful function test back up the whole system and hand the files to the cus tomer system administrator During a system restore...

Page 27: ...d reset 24 IP users 5 8 18 25 Jung TKM Client 5 Legal notice 4 Licences 25 Local access points 13 Log level 26 Logging 26 Login on the Gateway 12 16 18 22 Manual programming 10 15 Menu structure User interface 9 Mobile network connection 21 Multiple line system 8 Network characteristics 13 Observe the safety instructions 4 Operating software apps 13 Operational data 26 Optional commissioning steps...

Page 28: ...elefon und Telegrafenwerke OHG Postfach 1155 78113 Furtwangen Bregstraße 1 78120 Furtwangen Telefon 49 7723 63 0 Telefax 49 7723 63 300 www siedle de info siedle de 2017 11 19 Printed in Germany Best Nr 210009601 00 EN ...

Reviews: