User Manual
Modbus/BACnet IP Gateway
GT200-BM-2RS
WWW.SSTCOMM.COM
7
Mode
(Bit 1)
Function
(Bit 2)
Mode
Description
Off
Off
Run mode
BACnet IP and Modbus RTU data can be exchanged;
Allow reading and writing configuration data. After
reconfiguring GT200-BM-2RS, it needs to restart. Then, the
configuration will take effect.
Off
On
Run mode
BACnet IP and Modbus RTU data can be exchanged, prohibit
reading and writing configuration data.
On
Off
Configuration
Mode
IP address is fixed at 192.168.0.188; this mode can only read
and write configuration data but cannot communicate between
BACnetIP
and Modbus RTU
.
On
On
Configuration
Mode
IP address is fixed at 192.168.0.188; this mode can only read
configuration data but cannot communicate between
BACnetIP
and Modbus RTU.
Note: Restart GT200-BM-2RS (power off and power on) after reconfiguring the configuration and the
configuration will take effect!
2.4 Interface
2.4.1 Power Interface
GT200-BM-2RS uses a 24V DC power supply; it has two power interfaces with redundancy function. Users
can use one or two power supply.
GND
NC
24V+
1
2
3
Pin
Function
1
GND
2
NC (Not Connected)
3
24V+, DC