7 DeviceNet Network Configuration Instructions
(DeviceNet Adapter)
7.1 I/O Configuration
The configuration instructions in AB PLC when GT200-MT-DN is used as a DeviceNet adapter.
I/O input:
DeviceNet I/O input bytes can be configured as 8, 16, 32, 48, 64, 72, 96, 112, 160, 192, 224 bytes.
I/O output:
DeviceNet I/O output bytes can be configured as 8, 16, 32, 48, 64, 72, 96, 112, 160, 192, 224 bytes.
7.2 DeviceNet Parameters
Input Bytes: DeviceNet I/O connection input bytes.
Output Bytes: DeviceNet I/O connection output bytes
The above two parameters must be consistent with the configuration input/output bytes in the DeviceNet scanner
scan list of configuration software such as RSNetWorx, otherwise the connection will fail.
Keep Latest Data: "Keep Latest Data" means to keep the latest updated data of the disconnected side network, and
it is not cleared.