THE EXHAUST TERMINATION LOCATION MUST BE AT LEAST: (FIGURE 10)
1’ (305 mm)
ABOVE the Ground Level
7’ (2.1 m)
FROM a Public Walkway
1’(305 mm)
FROM The Wall Penetration point
3’ (915mm)
FROM a Gas meter/Regulator assembly
2’ (610 mm)
FROM any Adjacent Combustibles such as:
Adjacent buildings, Fences, Protruding parts
of the Structure, Roof Eaves or Overhangs,
Plants, Shrubs, etc.
Note: Certain local code restrictions may apply. Check with Local Officials first before
installing.
FIGURE 10.
VENTING: TERMINATION CLEARANCE REQUIREMENTS SIDE VIEW
(All dimensions show MINIMUM distances)