Normally Closed Switch - connects across terminals 8 and 9.
•
Terminal 7 has a limited amount of unregulated dc power available to power an LED
lamp to permit the use of a lighted switch for REPO. Contact Staco Energy Products
Company for details if you desire to use this feature.
Please also note that the Options Control Board in the MBS must be properly
configured for the normally closed REPO switch to work.
4.4.2 Terminal Strip Torque Requirements
The terminals on the Customer Low Voltage Connection Terminal Block must be torqued to
5.3 to 7.0 inch-lbs. The terminals on the Control Connections (on the UPS) must be torqued
to 4.4 inch-lbs.
Figure 5 – Standard Customer Low Voltage Connection Terminal Block
Figure 6 –Customer Low Voltage Connection Terminal Block with SKRU Option