background image

Page | 13 

SECTION 5   

 

Operation 

 
Refer to the User's Manual for the UPS   for instructions on operating the UPS part of the 
system.  

If the UPS is part of a parallel system, special operating instructions apply.   

 

Maintenance Bypass Switch (MBS) 

 
The purpose of the Maintenance Bypass Switch (MBS) is to facilitate servicing the UPS 
without removing power from the load.  The main functional components of the MBS are 
three circuit breakers that are used as disconnect switches. We will designate them 
“BKR1”, “BKR2”, and “BKR3”, but they are labeled “1”, “2”, and “3” above the breaker 
handles on the front inner cover of the cabinet.  The breakers each have three positions: off 
(down), on (up), and tripped (in between off and on).  To turn on a tripped breaker, reset 
the breaker by pushing the handle down to the off position, then raise it to the on position.  
If a breaker will not reset or trips as being turned on, the backfeed prevention interlock is 
active and the proper conditions (as described below) will have to be present before the 
breaker can be operated.  When closed, BKR1 supplies power from the supply (utility) to 
the bypass input of the UPS.  For single input UPS configurations, it also supplies power to 
the rectifier input.  When closed, BKR3 connects the output of the UPS to the load.  When 
closed, BKR2 bypasses the path through BKR1, the UPS, and BKR3 and connects the 
supply directly to the load.  BKR2 and BKR3 must never be closed at the same time unless 
the UPS is in bypass mode.  It does not matter which type of bypass, but bypass via 
SWMB is the simplest to engage.  There are signals that support an interlock function to 
prevent BKR2 from being closed unless BKR3 is open or the UPS is in bypass mode.  For 
the UPS to be able to issue this signal, the UPS controls must be powered.  Always 
observe proper switching sequence to avoid loss of power to the load  Common switching 
operations are also described, below.  There are also some problem scenarios listed. 
 
The three switches (Breaker 1, Breaker 2, and Breaker 3) have eight possible combinations 
or "States".  

Table 7

 lists all of the possible states.  Note that one possibility (Breaker 1 

open, Breaker 2 and Breaker 3 closed) is forbidden as unexpected system behavior could 
result, including loss of power to the load.  The Overlap State is a transient state.  It is the 
"make" before the "break".  Time spent in this state should be kept to a minimum as 
external events could lead to tripping Breaker 2, possibly interrupting power to the load. 
Also, please note that the UPS does not condition the power to the load while in bypass 
and that battery back-up is not available while in bypass. 
 
To avoid damage to the UPS and to avoid interrupting power to the load, the procedures 
listed in 

Table 8

 must be used to change from one state to another.  The MBS is equipped 

with a label (see 

Figure 8

) that describes the breaker sequences for two common 

operations.  The "To place load on maintenance bypass" sequence describes going from 
Normal State to Overlap to UPS Unloaded to Maintenance.  The "To place load on UPS" 
sequence describes going from Maintenance State to UPS Unloaded to Overlap to Normal. 
 

 

Summary of Contents for FLU-160-00

Page 1: ...003 2621 FIRSTLINE P Maintenance Bypass Switch Cabinet 160kVA 250kVA 480V Input Output With SKRU USER MANUAL...

Page 2: ...e P Maintenance Bypass Switch Technical Specifications 18 Table 1 Symbols 4 Table 2 Model Floor Loadings 5 Table 3 Wire Size Requirements 10 Table 4 Recommended Crimp Lugs 10 Table 5 Maximum Current R...

Page 3: ...the top and the bottom for maximum flexibility in wiring the source and load power connections Please refer to Figure 1 for the outline drawing of the cabinet All dimensions in Inches millimeters Fig...

Page 4: ...net MBS than is required for the UPS but special installation requirements must be met the power source connected to the MBS must include circuit protection as specified for the input in the UPS manua...

Page 5: ...vent the possibility of backfeed Read and follow the instructions that came with the associated UPS or emergency lighting system before operating this equipment DANGER This equipment contains lethal v...

Page 6: ...ould only be performed by qualified service personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries Read understand and follow all instruction...

Page 7: ...carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative Floor Loading When planning the installation consider the cabinet wei...

Page 8: ...t strap or similar device of sufficient strength to tie the upper part of the cabinet to the forklift tower before moving 5 Keep people out of the fall zone If the cabinet topples over stand clear 6 W...

Page 9: ...binet 1 Remove right side panel of UPS and save hardware 2 Butt left side of MBS cabinet up against the right side of the UPS 3 Bolt the cabinets together at 6 locations with the supplied 5 16 hardwar...

Page 10: ...the equipment is the proper type The equipment covered by this manual is 480 V 60 Hz input and output only The Maintenance Bypass Switch Cabinet MBS can be used in delta delta or wye wye applications...

Page 11: ...BREAKER PANELBOARD 1 BREAKER PANELBOARD 2 BREAKER DISPLAY ALARM TEMP ALARM TO UPS REQUEST BYPASS INPUT FRONT PANEL TRIP SWITCH KEYLOCK RELEASE ON BYPASS TRANSFORMER TEMP SWITCHES HT OT REPO SWITCH EXT...

Page 12: ...e Connectors Thomas Betts Single Hole Connectors 3 8 2 0 54210 54110 3 0 54211 54111 4 0 54212 54112 250 kcmil 54213 54174 300 kcmil 54214 54179 350 kcmil 54215 256 30695 112 400 kcmil 54216 54116 500...

Page 13: ...r terminal pads to the load The load may be an external distribution panel etc If neutral is not needed by the load then it does not need to be supplied The wire must be in compliance with Table 3 and...

Page 14: ...a shielded cable with three twisted pairs and is available from a number of sources in various spool lengths Two pairs are required Pair 1 First wire from terminal 2 of the Low Voltage Connection Ter...

Page 15: ...ode It does not matter which type of bypass but bypass via SWMB is the simplest to engage There are signals that support an interlock function to prevent BKR2 from being closed unless BKR3 is open or...

Page 16: ...on Bypass lamp will flash and the inverter will stop and battery supported operation is no longer possible 3 Close BKR2 4 Open BKR3 5 Shut down the UPS if desired by opening SWOUT SWIN SWBY and open t...

Page 17: ...he load is powered via BKR2 MBS mode A fault in the UPS could cause the upstream circuit protection circuit breaker or fuse to operate removing power from both the faulted UPS input and the MBS input...

Page 18: ...eaker 1 Breaker 2 Breaker 3 Adjacent State s Normal closed open closed Overlap Test UPS Test Battery Overlap closed closed closed Normal UPS Unloaded UPS Unloaded closed closed open Overlap Maintenanc...

Page 19: ...Verify load on bypass by observing front panel of UPS 3 Close Breaker 3 UPS Unloaded Maintenance 1 Turn Off UPS 2 Open Breaker 1 Maintenance UPS Unloaded 1 Close Breaker 1 2 Turn On UPS Maintenance L...

Page 20: ...minations usually are the sign of a loose connection but can also signal that a breaker is failing Loose connections should only be serviced after removal of power If the system is powered down consid...

Reviews: