background image

 

26

 
 
 
V1 

 
 
 
                               

* It shows the UPS is operated in “normal mode”. 

 

 

 

 

V2 

 
 
 

                               

* It shows the UPS is operated in “Eco mode”. 

 

 

 

 

 

V3 

 

 

 

* It shows the UPS is operated in “CVCF 50Hz mode”. 

P.S: If you want to set be a frequency converter, it shall be required by a qualified technician. 

 
 
 
 
V4 

 

 

* It shows the UPS is operated in “CVCF 60Hz mode”. 

P.S: If you want to set be a frequency converter, it shall be required by a qualified technician. 

 

 
 
 

 

 
 

* It shows Output Voltage Adjustment % from 0% to 3% or -0% to -3%.   

 

27

 
 
 
 

 
 
 

* It shows UPS Identification Number.   

 

 

 

 

 
 

 

* It shows the UPS is in the No. 1

st

 of parallel systems.   

 
3.5.4.3  Press scroll up 

  key pa d, you  ma y exe cute s pecial  functions.  The 

Functions i ncludes bu zzer ON  (a s dra wing Q1 ),  or  buzzer  OFF  (as 

drawing  Q2,  Alarm  silence  for UP S W arning) an d se lf-test OFF ( As 

drawing R1) or self-test ON. (as drawing R2. UPS will execute battery 

test for 10 seconds. If the self-test is successful, it will show as Drawing 

E1; otherwise, it will show as drawing E2 & error message in the same 

time.) 

 

3.5.5 

UPS Default Settings and their alternatives 

 

3.5.5.1  Make s ure  the U PS  is no t  “On” ye t. Pr ess  On Sw itch 

 an d  scroll 

down 

  k ey pads simultaneously

 

for approx. 3 s econds, the buzzer 

will sound twice, the LCD display screen shows as drawing Q1, then the 

UPS is under setting mode now. 

 

3.5.5.2  To scroll down the LCD screen, you may refer to Chapter 3.5.4.2   

Summary of Contents for SC60021RM

Page 1: ...king 11 3 2 Selecting Installation Position 12 3 3 Installation of Casters Cover 13 3 4 Terminal Block Explanation 18 3 5 Operation Test and Installation Instruction 19 4 Troubleshooting Guide 30 4 1...

Page 2: ...ntrol medical and security applications Non authorized technician is not allowed to install the UPS in the following areas a Medical equipment directly related to human life b Elevator Metro Subway sy...

Page 3: ...condition ceases 2 1 5 Should t he output becomes sho rt circuit th e U PS ho lds th e system and cuts the output automatically till the short circuit situation is removed manually 2 1 6 Should the un...

Page 4: ...tem desired to be measured 14 UPS ON Switch or Alarm Silence 15 UPS OFF Switch 16 Previous Page or Setting Change 7 17 Next Page 18 Special Function Log in out 19 Enter or Reconfirmed 20 Utility Input...

Page 5: ...working under ECO Economic Line interactive mode UPS Fault or Abnormal UPS ON Alarm Silence UP S OFF Switch Sp ecial functions log in out Go to next page Go to previous page or change the setting of...

Page 6: ...ll get the highest priority in control command then the SNMP WEB card then R2E RSE and USE get the lowest priority 2 4 1 True RS232 type 2 4 1 1 The RS232 interface settings The RS232 interface shall...

Page 7: ...r flow to the ventilation openings of the unit 3 Please check the installation site to avoid overheat and excessive moisture 4 Do not place the UPS in an environment near dust corruptive or salty mate...

Page 8: ...installation step 3 3 2 1 Power Module Battery Module Step 1 Installation Power Isolation Transformer and Battery Step 1 Installation Ear Cover S3 B1 B2 S4 B1 B3 S4 15 Step 2 Installation Ear Cover to...

Page 9: ...3 3 2 2 Power Module Isolation Transformer Module Battery Module Step 4 Installation Battery Module to Step 1 Installation Isolation Transformer Module to Rail 17 Step 2 Installation Power Module to R...

Page 10: ...SET OUTPUT BREAKER PUSH TO RESET OUTPUT 20A MAX OUTPUT 30A MAX 20AMAX 15A MAX OUTPUT BREAKER PUSH TO RESET 15A MAX 30A 20A 19 3 5 Operation Test and Installation Instruction 3 5 1 Start Up in Normal M...

Page 11: ...charged 3 5 2 Start up in Battery Mode Cold Start 3 5 2 1 Make sure the UPS you have has already been installed at least 1 set 20pcs of 12V 7AH or 12V 5AH batteries 3 5 2 2 Push the UPS On Switch to a...

Page 12: ...s Input Drawi ng J Frequency from Utility Input Drawing K Frequency fr om B ypass I nput Drawing L UPS Ou tput Vo ltage Drawing M UPS Output Frequency Drawing N UPS Output Load Drawing O UPS Battery V...

Page 13: ...ween Drawing Q1 buzzer Drawing R1 Self test Drawing S1 Bypass Voltage Windows D rawing T O utput Fre quency Synchronization Window Drawing U Inverter Output Voltage Drawing V1 UPS Operation Mode Drawi...

Page 14: ...scroll up key pad you may execute special functions The Functions i ncludes bu zzer ON a s dra wing Q1 or buzzer OFF as drawing Q2 Alarm silence for UP S W arning an d se lf test OFF As drawing R1 or...

Page 15: ...ng A A and a ab normal message will show in the LCD screen 3 5 6 2 To release the UPS lock please proceed the followings Check those error messages recorded C heck to s ee Ch apter 2 2 to tr ouble s h...

Page 16: ...erwise consult your local distributor right away 2 Remove some uncritical load at the UPS output end If any damage of the coating of AC power cord please replace a new one 3 Remove the short circuit o...

Page 17: ...gnments of the EPO are 1 EPO 2 Ground 6 1 1 To enable the EPO function please short Pin 1 2 6 2 R2E 2nd RS 232 card 6 2 1 CN1 is for RS232 DB9 and CN3 is for EPO 6 2 2 For communication protocol pleas...

Page 18: ...shutdown function please short Pin 8 10 6 5 4 Adapted flat cable cable A or cable B 6 5 5 For installation please refer to Chapter 6 7 1 VCC 5V 2 D 3 D 4 Ground 35 6 6 SNMP Cards 6 6 1 SNMP WEB card...

Page 19: ...1 Unscrew the flank of the battery bank front panel as indicated in Step 1 2 Remove the front panel as indicated in Step 2 3 Remove the screw of the battery pack as shown in Step 3 4 Unplug the hot s...

Page 20: ...l Load DC Start Yes Cooling Variable Speed Fans load determines speed DISPLAY ALARMS DIAGNOSTICS COMMUNICATIONS Status On LED LCD Line Mode Backup Mode ECO Mode Bypass Supply Battery Low Battery Bad D...

Page 21: ...of installation max 42 months from ship date for UniStar III and two 2 year from date of installation max 30 months from ship date for UniStar III P Please read your Warranty carefully This Warranty...

Page 22: ...nd supersede all previous warranties Staco reserves the right to supplement or change the terms of this Warranty in any subsequent warranty offering to User or others In the event that any provision o...

Reviews: