2
1 Important
Safety Instruction
1.1. An Important Notice
1.1.1
To ensure safety in all applications where a UPS is hard wired to the Electrical Supply, ensure
that the system is installed by a Qualified Electrical Contractor.
1.1.2
1.1.2The UPS has its own internal energy source (battery). Should the battery be switched on
when no AC power is available, there could be voltage at the output terminals.
1.1.3
Make sure that the AC Utility outlet is correctly grounded.
1.1.4
Do not open the case, as there are no serviceable parts inside. Your Warranty will be void.
1.1.5
Do not try to repair the unit yourself; contact your local supplier or your warranty will be void.
1.1.6
Please make sure that the input voltage of the UPS matches the supply voltage.
1.1.7
Use a certified input power cable with the correct plugs and sockets for the appropriate voltage
system.
1.1.8
To eliminate any overheating of the UPS, keep all ventilation openings free from obstruction,
and do not store "things" on top of the UPS. Keep the UPS 30 cm away from the wall.
1.1.9
Make sure the UPS is installed within the proper environment as spe cified. (0-40
℃
and 30-
90% non-condensing humidity)
1.1.10
Do not install the UPS in direct sunlight. Your warranty may be void if the batteries fail.
1.1.11
Install the UPS indoors as it is not designed for installation outdoors.
1.1.12
Dusty, corrosive and salty environments can do damage to any UPS.
1.1.13
Install the UPS away from objects that give off excessive heat and areas that are excessively
wet.
1.1.14
If liquids are split onto the UPS or foreign objects dropped into the unit, the warranty will be
null and void.
1.1.15
The battery will discharge naturally if the system is unused for any length of time.
1.1.16
It should be recharged every 2-3 months if unused. If this is not done, then the warranty will be
null and void. When installed and being used, the batteries will be automatically recharged and
kept in top condition.
3
1.1.17
This U PS sup ports electr onic eq uipment in offices, telecommunications, p rocess co ntrol,
medical and security applications. Non-authorized technician is not allowed to install the UPS
in the following areas.
a. Medical equipment directly related to human life
b. Elevator, Metro (Subway) system or any other equipment related to
hu man safety.
c. Public system or critical computer systems.
1.1.18
Do not install the UPS in an environment with sparks, smoke or gas.
1.1.19
Make sure the UPS is completely turned off when moving the UPS from one place to another.
It might cause electrical shock if the output is not cut completely.
1.1.20
The Maintenance Bypass S witch is eq uipped w ith th e UP S. Plea se fo llow th e pr ocedures
strictly to switch on/off the Maintenance Bypass Switch. It is built onto a separate Rack Tower
cabinet with the galvanic isolation transformer.
1.1.21
The U PS of fers C VCF (Constant V oltage C onstant Frequency) sett ing fu nction. To set R T
series to be a CVCF shall be required by a qualified technician.
a. For correct setting and wiring, please contact with your local agent.
b. Do not do it by yourself; otherwise, your warranty will be void.
1.1.22
This UPS has b een designed and constructed to protect your assets from the w ide range of
power aberrations experienced on U tility power lines to day. I t is y our insurance for re liable,
clean and stable voltage supply. It is w orth taking care to install the system correctly and to
have it maintained correctly by your local dealer.
1.1.23
SAVE THESE INSTRUCTIONS - T his Manual Contains Important Instructions that should be
followed during Installation and Maintenance of the UPS and Batteries.
1.1.24
Intended for Installation in a Controlled Environment.
1.1.25
CAUTION - A disconnect switch shall be provided by others for ac output circuit. To reduce the
risk of fire, connect only to a circuit provided with branch circuit overcurrent protection for 30
amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.
1.1.26
CAUTION - To reduce the risk of fir e, unit input connect only to a circuit provided with branch
circuit ove rcurrent p rotection f or 40 a mperes r ating in acco rdance w ith the National Electric
Code, ANSI/NFPA 70.
1.1.27
Use No. 10 AWG, 60
°
C copper wire and 22.1 lb-in Torque force when connecting to te rminal
block.