6.2 230V Specifications
MODEL (SCV)
10002
10002-LB
15002
15002-LB
20002
20002-LB
30002
30002-LB
Capacity
VA
1000 VA
1500VA
2000 VA
3000 VA
W
900 W
1350W
1800 W
2700 W
INPUT
Voltage
Range
Rated
voltage
220-240 VAC
Low Line
Transfer
160 VAC/140 VAC/120 VAC/110 VAC ± 5 %
(based on load percentage 100%-80% / 80%-70% / 70%-60% / 60%-0)
Low Line
Comeback
170 VAC / 150 VAC / 130 VAC / 120 VAC ± 5 %
High Line
Transfer
300 VAC ± 5 %
High Line
Comeback
290 VAC ± 5 %
Frequency Range
40Hz ~ 70Hz
Power Factor
≧
0.99 @normal voltage
OUTPUT
Output Voltage
200/208/220/230/240 VAC
AC Voltage Regulation
± 1%
Frequency Range
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range
50Hz
±
0.5% or 60Hz
±
0.5% (Bat. Mode)
Current Crest Ratio
(CF)
5:1 (max.)
Harmonic Distortion
(THDU)
≦
2% (Linear load)
6% max (Batt. mode before shut down)
Transfer
Time
AC to DC
Zero
Inverter to
Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sine wave
EFFICIENCY
AC Mode
87%
87%
88%
88%
Battery Mode
85%
85%
86%
85%
ECO Mode
94%
94%
95%
97%
BATTERY
Battery Type
12V/9Ah
Depending
on application
12V/9Ah
Depending on
application
12V/9Ah
Depending on
application
12V/9Ah
Depending on
application
Numbers
2
3
4
6
Typical Recharge Time
4 hours recover to 90% capacity (for standard model only)
Charging Current
(max.)
1 A
1A/2A/
4A/8A
1 A
1A/2A/
4A/8A
1 A
1A/2A/
4A/8A
1 A
1A/2A/
4A/8A
Charging Voltage
27.4 VDC ± 1%
41.1 VDC ± 1%
54.7 VDC ± 1%
82.1VDC ± 1%
INDICATORS
LCD
UPS status, Load level, Battery level, Input/Output/battery info, Discharge time and Fault indicators
ALARM
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
PHYSICAL
Dimension, DxWxH (in)
16.44 x 17.24 x 3.39
20.38 x 17.24 x 3.39
20.38 x 17.24 x 3.39
25.10 x 17.24 x 3.39
Net Weight (lbs)
28
19
39
24
45
24
65
30
ENVIRONMENT
Humidity
20-90 % RH @ 0- 40°C (non-condensing) (32°F - 104°F)
Noise Level
Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 80% when the output voltage is adjusted to 200VAC/208VAC.