3.5.7 Turn off the UPS with utility power supply in Line mode
1. When LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn
Off”;
2. Move the arrow to “Yes” by up or down button, then press “ON/ENTER”;
UPS will be turning off to bypass mode while beeping once. You could also enter the “control
menu” to select the instruction “Turn Off” to turn off the UPS. See
NOTE:
“Turn Off” means that UPS is not working on line / converter / ECO / battery / battery test
mode. So even though the UPS is turned off, if input or bypass voltage is normal, the internal
power supply will still be working; if bypass status has been set to “enable”, the output voltage
of the UPS will still exist.
3. To fully cut off the output, please switch off the external input breaker. A few seconds later, there
is no display shown on the panel and UPS is completely off.
3.5.8 Turn off the UPS without utility power supply in Battery mode
1. When LCD is on home page, press the “OFF/ESC” button, LCD will show a prompt page of “Turn
Off”;
2. Move the arrow to “Yes” by up or down button, then press “ON/ENTER”;
UPS will be turning off to bypass mode while beeping once. You could also enter the “control
menu” to select the instruction “Turn Off” to turn off the UPS. Please refer to the section of
“LCD operation”.
3. If there is no bypass input voltage, the UPS will cut off all power supply and there is no display
shown on the panel.