Isolating Repeater Field Circuit Ex i
Series 9165
8.2.3 Mounting / Dismounting on pac-Carrier
See operating instructions for pac-Carrier Type 9195.
8.2.4 Mounting / Dismounting pluggable Terminals
Mounting
• Plug the terminal into the device until the terminal engages.
Dismounting
8.3
Installation
8.3.1 Electrical Connections
8.3.2 Schematic Diagrams
See device labelling.
8.3.3 Connection of Supply
10859E00
• Position the screwdriver behind the terminal.
• Push out the terminal.
Operation under difficult conditions, such as, in particular, on ships,
requires additional measures to be taken for correct installation,
depending on the place of use. Further information and instructions
on this can be obtained from your regional sales contact on request.
DANGER
Explosion hazard caused by too high voltage!
Non-compliance results in severe or fatal injuries.
• Connect the device only to equipment with internal voltage
U
m
: max. 253 V AC / 50 Hz.
DANGER
Explosion hazard due to incorrect safety characteristic values of the
device or connected field devices!
Non-compliance results in severe or fatal injuries.
• Check safety characteristic values of the device and connected
field devices according to the national installation guidelines.
Type of supply
Connection
Direct supply of the device via 24 V connection
Green terminals "7+" and "9-"
Supply via pac-Bus
pac-Bus terminals "1+" and "2-"