279954 / 944260310110
2022-05-04·BA00·III·en·00
Product Selection and Project Engineering
11
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
CPU module for Zone 1
Series 9442/32
5.4
Redundancy
The IS1+ Remote I/O system can also be implemented redundantly based on the
communication protocol. Here, a distinction is made between CPU redundancy,
power redundancy and system/full redundancy.
The following table shows the components required for the respective redundancy concepts:
Comply with the specifications for selecting the suitable 9496/32 socket and maximum
equipping of the 9442/32 CPU module and 9445/32 power module!
9496/32 socket
9442/32 CPU module 9445/32 power module
No
redundancy
With 3 slots
1 x CPU module
(applies for all
protocols)
1 x power module
CPU
redundancy
With 3 slots
2 x CPU module
(PROFIBUS DP,
Modbus TCP)
1 x power module
Power
redundancy
With 3 slots
1 x CPU module
(applies for all
protocols)
2 x power module
System/
full redundancy
With 4 slots
2 x CPU module
(PROFIBUS DP,
Modbus TCP)
2 x power module
23098E00
No
redundancy
CPU
redundancy
Power
redundancy
System/
full redundancy