Product Selection, Project Engineering and Modification
15
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Ex d enclosure made of aluminium/flameproof enclosure
8250/0 series empty enclosure,
8250/1 series terminal box,
8250/5 series control panel/control station
5.3.2 Additional Terminals
Fitting of additional terminals by the customer
▶
Modify the device carefully and only in accordance with the safety notes
(see the "Safety" chapter).
▶
Ascertain additional clamping units, terminal type, quantity, cross section and current load
(see the "Technical data" chapter).
▶
Check whether the rating plate data changes due to retrofitting
(cross section, voltage, current, etc.).
▶
Check whether enough space and fastening options are available for equipping.
5.3.3 Additional internal Built-In Components
If the installation conditions are not observed, retrofitting is not permitted!
Only R. STAHL may fit additional built-in components. Any components attached by the
customer must be subjected to individual acceptance testing by R. STAHL or a notified
test body (third-party inspection).