Operation, Installation and Maintenance Manual for 6018/11 - Series
ID-No.:
226765 / 6018605300
Publication Code: 2017-08-31:BA00.lll.en.02 Page - 12 - of 22
•
The terminal cover of optional screw-type terminals does not have to be removed to clamp the conductor!
7.3.3.1
Connection terminals
Standard:
Spring clamp terminals
0.5 to 4 mm
2
Solid / Stranded
Stripping length:
10 ... 11 mm
Optional:
Screw-type terminals
0.5 to 4 mm
2
finely and extra
finely stranded, and 0.5 to 6 mm
2
solid
Stripping length:
10 ... 11 mm
L1, L2, L3 = Phase
L
I
= Switched Phase
N
= Nuetral Conductor
PE
= Protective conductor
7.3.3.2
Operating Modes:
Power supply operation
Stand-by operation
The lamps are switched off regardless of normal lighting.
Continuous operation
The lamps are switched on regardless of normal lighting.
Normal lighting operation
The lamps are operated by normal lighting.
Emergency light operation:
In the event of a power failure, the light fitting switches to emergency light operation. Emergency lamp
•
is marked with a green dot on the lamp holder.
•
is switched on regardless of the operation mode of the selected emergency light operating time.
If the emergency lamp is defective, the light will be switched to the secondary lamp.
Emergency light operation time
Emergency light
operation time
Jumper between terminals 11 and 12 of
the emergency light electronics
1.5 hours
Open (Delivery State)
3.0 hours
Closed