Operation, Installation and Maintenance Manual for 6018/11 - Series
ID-No.:
226765 / 6018605300
Publication Code: 2017-08-31:BA00.lll.en.02 Page - 14 - of 22
Normal lighting operation
In this condition, the light fixture is switched ON continuously as long as the supply is ON and the emergency mode will take
over when the mains Fails.
Connection version remote switch
The remote switch is directly connected to the emergency light electronics 6043/7.
The following connection versions are possible:
Point-to-point connection
Linear connection
NOTE
The following conductor specifications must be observed during connection.
Point-to-point connection
Linear connection
Maximum conductor length
x 1
x 2
x 3
500 m
100 m
50 m
500 m
Maximum number of light fittings
50
30
Minimum cable cross-section
1.5 mm
2
1.5 mm
2