Commissioning
14
131955 / 8070603300
S-BA-8070/1-02-en-29/10/2008
Position Switch
8070/1
Back-Up Fuses
For short-circuit protection, a back-up fuse rated at max. 10 A with tripping characteristic
gL/gG according to IEC 60269-1 may be used.
Instructions regarding cable connections and contact replacement
X
Dismantle 50 mm of the wire and strip 6 mm of the conductor insulation.
X
Open cover.
X
Insert the wire into the cable entry and connect it to the contact.
X
Close cover.
X
Tighten the cable glands (tightening torque see "Technical Data").
10 Commissioning
Before commissioning the device, ensure that:
X
the device has been installed according to the directions
X
the device is not damaged
X
connections have been made correctly
X
all screws and nuts are fully tightened
X
the terminal compartment is clean
X
there are no foreign bodies inside the device
X
the cables and wires have been inserted correctly
X
the cable glands and stopping plugs are securely tightened
X
no part of the flameproof enclosure is damaged
11450E00
)
Do not use the switch as a mechanical stop. Secure the limit switch against
position change by means of a locking device.