Mounting / Dismounting
Mount the device carefully and only in accordance with the safety notes
(see Chapter "Safety").
Read through the following installation conditions and assembly instructions carefully and
follow them precisely.
6.1.1 Operating Position
The operating position is optional.
6.1.2 Environmental Installation Conditions
A protective roof or wall can be provided if the explosion-protected device will be exposed
to the elements outdoors.
Equip explosion-protected electric equipment with a breather and drain valve in order to
prevent the vacuum effect.
Do not create any cold bridges (condensation hazard). If necessary, install the enclosure
with a clearance to minimise condensation in the enclosure.
6.2
Installation
Operation under difficult conditions, such as on ships or in strong sunlight,
requires additional measures to be taken to ensure that the device is installed correctly,
depending on the operating location. Further information and instructions on this can be
obtained from your regional sales contact upon request.
DANGER! Explosion due to intense heating inside the enclosure!
Non-compliance may result in serious or even fatal injuries.
Ensure that distances between Ex e electric circuits and Ex i electric circuits comply
with standards (EN IEC 60079-11).
Select suitable conductors that do not exceed the permissible heating temperature
within the enclosure.
Pay attention to the specified cross-sections.
Attach the core end sleeves properly.
DANGER! Explosion due to improper installation!
Non-compliance may result in serious or even fatal injuries.
Install the device carefully and only in accordance with the safety notes
("Safety" chapter).
The installation steps stated below must be carried out very precisely.
The necessary technical details/data on electrical installation can be found in the
following documents:
"Technical data" chapter in these operating instructions
Documentation and data sheets provided by the terminal manufacturers
Documentation and data sheets for the installed devices (e.g. for specifications with
regard to equipotential bonding, earthing and intrinsically safe circuits)