Junction Boxes
Series 8118
5
Technical Data
Explosion Protection
Global (IECEx)
Versions
junction box without
miniature fuse
junction box with
miniature fuse
Type
8118/.11
8118/.21
8118/.31
8118/113
8118/123
8118/133
Gas and dust
IECEx PTB 06.0026
IECEx PTB 06.0026
Ex eb ia [ia Ga] ib mb IIC, IIB, IIA
T6...T4 Gb
Ex eb mb IIC T* Gb
* depending on the
miniature fuse in use
Ex tb IIIC T80°C ... T130°C Db
Ex tb IIIC T80°C ... T130°C Db
Europe (ATEX)
Gas and dust
PTB 99 ATEX 3103
PTB 99 ATEX 3103
E
II 2(1) G Ex eb ia [ia Ga] ib mb
IIC, IIB, IIA T6...T4 Gb
E
II 2 G Ex e mb IIC T* Gb
* depending on the
miniature fuse in use
E
II 2 D Ex tb IIIC T80°C...T130°C Db
E
II 2 D Ex tb IIIC T80°C...T130°C Db
Certifications and certificates
Certificates
IECEx, ATEX, Brazil (INMETRO), China (China-Ex), India (PESO),
Kazakhstan (TR), Korea (KCs), Russia (TR), Ukraine (TR),
Belarus (TR)
Technical Data
Electrical data
Versions
junction box without
miniature fuse
junction box with
miniature fuse
Type
8118/.11
8118/.21
8118/.31
8118/113
8118/123
8118/133
Rated operational
voltage
550 V
750 V
750 V
250 or 500 V ,
(depending on
miniature fuse used)
Connection
Terminals
Current carrying
capacity at
conductor
cross-section of
max. 24 A
4 mm
2
max. 32 A
6 mm
2
max. 44 A
10 mm
2
max. 24 A
4 mm
2
max. 32 A
6 mm
2
max. 44 A
10 mm
2
Max. number of
miniature fuses
–
–
–
1 x 8560
2 x 8560
2 x 8560