Motor Protection Circuit Breaker
Series 8146/5-V27
For further technical data, see www.r-stahl.com.
6
Transport and Storage
• Transport and store the device only in the original packaging.
• Store the device in a dry place (no condensation) and vibration-free.
• Do not drop the device.
Shunt release
Electrical data
Function
Used for tripping the moulded case circuit breaker remotely
by applying an actuating voltage
Pick-up voltage
)
0.85 x U
c
Relative duty cycle Switches off automatically via integrated contact switch
Power
consumption
Inrush
24 to 60 V: 14.4 to 90 VA;
110 to 240 V: 13 to 61 VA;
220 to 415 V: 17.6 to 62.3 VA
Holding
Switches off automatically via integrated contact switch
Ammeter
Device version
Type 8405, front dimensions 64 mm x 64 mm
Electrical data
Movement
Moving iron measuring instrument, class 2.5; direct measuring
Measuring range
Depending on the adjustment range of the switch
Overload capacity 1 A variant: 50 A
(50xI
N
1 s)
4 A variant: 200 A
(50xI
N
1 s)
10 A variant: 500 A
(50xI
N
1 s)
15 A variant: 450 A
(30xI
N
1 s)
Technical Data