Terminal Box
Series 8150/1, Series 8150/2
5.4.3 Fuses
When fitting fuses, the ambient temperature values for the following temperature classes
apply:
When fitting fuses, the ambient temperature values for areas with dust explosion hazard
for the following max. permissible surface temperatures apply:
6
Mounting and installation
6.1
Mounting/dismounting, operating position
Mount the device carefully and only in accordance with the safety notes (see chapter 3).
Read through the following installation conditions and assembly instructions carefully and
follow them precisely.
6.1.1 Operating position
Mount the device using the mounting straps. Refer to the dimensional drawing for
the dimensions of the mounting holes.
14282E00
Installing, modifying or retrofitting fuses is only permitted to be performed by R. STAHL!
Fuse current value
Temperature class
(
4 A
T6
> 4 A ... ( 5 A
T5
> 5 A ... ( 6.3 A
T4
Fuse current value
Ambient temperature
(Ta)
Max. permissible
surface temperature
(
4 A
(
40 °C
T80°C
(
4 A
(
56 °C
T95°C
(
5 A
(
46 °C
T95°C
(
6.3 A
(
70 °C
T130°C
DANGER! Explosion due to incorrect mounting position!
Non-compliance results in fatal or severe injuries.
Mount the device only on the floor or wall, not overhead or in a free-standing
position.
Mount the device torsion-free only on a level surface.
25
7 [0,28]
18 [0,71]
26 [1,02]
20
X
ø [ø 0,28]
7
[0,98]
[0,79]