204166 / 848560300010
2021-08-06·BA00·III·en·12
Appendix A
31
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Grounding monitoring device
Series 8485
14
Appendix A
14.1 Technical Data
Explosion protection
Global (IECEx)
Gas and dust
IECEx FTZU 15.0031X
Ex db ib [ib] IIB T4 Gb
Ex ib [ib] tb IIIC T130 °C Db
Europe (ATEX)
Gas and dust
FTZU 09 ATEX 0059X
E
II 2 G Ex db ib [ib] IIB T4 Gb
E
II 2 D Ex ib [ib] tb IIIC T130 °C Db
Certifications and certificates
Certifications
IECEx (FTZU), ATEX (FTZU), EAC (ENDCE), India (PESO)
Further parameters
Installation
in Zones 1, 2, 21, 22
Technical data
Electrical data
Number of channels 1
Operating mode
selection
Detection of road tanker, rail vehicle or FIBC (big bag)
Selection via DIP switch
Frequency range
47 to 63 Hz
Parameterisation
IrDA and Bluetooth
Auxiliary power
Nominal voltage
Nominal voltage range AC: 20 to 230 V
Nominal voltage range DC: 20 to 300 V
Nominal current
50 mA
Power
consumption
10 VA
Output
Limit contact
up to 4 change-over contacts
Min. load
condition
10 V DC / 100 mA
Max. load
condition AC
230 V AC / 3 A
Max. load
condition DC
230 V DC / 0.25 A 40 V DC / 3 A
Summary of Contents for 8485 Series
Page 73: ......