Technical Data
6
149909 / 8562604300
S-BA-8562-03-en-20/11/2008
Miniature Circuit Breaker
8562/5
Rated switching capacities
Breaking capacity
6 kA resp. 10 kA (25 kA to IEC)
Version
Circuit breaker, current limiting with thermal and magnetic release
Characteristics
Back-up protection
Poles
Series with 6 kA
Series with 10 kA
Voltage
(V)
Current
(kA)
Voltage
(V)
Current
(kA)
AC to IEC/EN 60898
1 - 4
I
cn
/
I
cs
230 / 240
6
I
cn
230 / 240
10
AC to IEC/EN 60947-2 1
I
cu
240
10
I
cu
240
15
1+N,
2
I
cu
127
30
I
cu
127
40
240
20
240
30
415
10
415
15
3, 4
I
cu
240
20
I
cu
240
30
415
10
415
15
DC to IEC/EN 60947-2
(Time constante 15
ms)
1
I
cu
/
I
cs
60
20
I
cu
/
I
cs
60
25
2
125
25
125
30
Characteristic
to EN 50898
B
C
D
Rated current range
6 A ... 32 A
0,5 A ... 32 A
0,5 A ... 32 A
Loads
> Elektric heatings
> Lighting
> Socket outlet
circuits
> Control circuits
e.t.c.
> Operating equipment
> Light fitting groups
> Motors
> Transformers
e.t.c.
> Operating equipment
> Motors with heavy
starting characteristic
e.t.c.
Normal temperature
30
o
C
30
o
C
30
o
C
Thermal overload trip
1,13 ... 1,45 I
n
1,13 ... 1,45 I
n
1,13 ... 1,45 I
n
Thermal overload trip
135% UL
--
1,13 ... 1,35 I
n
--
Magnetic trip
3 ... 5 I
n
3 ... 10I
n
3 ... 20I
n
Following MCBs
Type
MCB tripping
characteristic
C, D
B
B, C, D
Rated current
I
th
(A)
Preceding fuse type gG
Minimal rated current (A)
Maximal rated
current (A)
8562/5
1
4
- -
- -
2
8
63
3
10
6
20
10
80
10
25
16
16
40
20
20
50
32
100
25
63
40
32
80
50
40
100
50
125
Summary of Contents for 8562 Series
Page 2: ......
Page 3: ...Betriebsanleitung Leitungsschutzschalter 8562 5 ...
Page 17: ...Operating Instructions Miniature Circuit Breaker 8562 5 ...
Page 31: ......
Page 32: ...149909 8562604300 S BA 8562 03 de en 20 11 2008 ...