Installation
10
149909 / 8562604300
S-BA-8562-03-en-20/11/2008
Miniature Circuit Breaker
8562/5
8.2 Rated connection cross-section
Solid, stranded or finely stranded copper wires can be used. 1 or 2 wires of the same
cross-section can be fitted under one terminal. Both wires must be made of the same ma-
terial. No preparation is necessary prior to connecting the wires.
8.3 Connection diagrams
)
When terminal sleeves are fitted, they must be gas-tight and applied with a suitable tool.
Conductor
Main contact terminals
Auxiliary contact terminals
single-wire
2 x 1.5 ... 10 mm
2
*
2 x AWG 16 to 8
04935T00
2 x 0.75 ... 2.5 mm
2
2 x AWG 18 to 13
04937T00
1 x 10 mm
2
(bend the end of the conduc-
tor)
04938T00
04939T00
stranded or flexible-stran-
ded
2 x 1.5 ... 6 mm
2
2 x AWG 16 to 10
04940T00
2 x 0.75 ... 1.5 mm
2
2 x AWG 18 to 16
04941T00
Permissible tightening tor-
ques for the options mentio-
ned*
1.8 ... 2.0 Nm
16 ... 18 lb.in
1.0 ... 1.2 Nm
9 ... 11 lb.in
*Permissible tightening tor-
ques for 10 mm
2
single-wire
cable
2.5 Nm
23 lb.in
Schematic
07614E00
07613E00
07612E00
07611E00
1-pole
1-pole + N
2-pole
3-pole
07610E00
11537E00
11536E00
07618E00
3-pole + N
4-pole
Auxiliary contact 1 CO
Fault indication contact 1 CO
96
95
98
05
06 08