149909 / 8562604300
S-BA-8562-03-en-20/11/2008
Commissioning
11
Miniature Circuit Breaker
8562/5
The device may be connected from the top or the bottom side. It has to be taken care that
the neutral conductor is connected correctly.
Exception: 8562/5.-.15.-... and 8562/5.-.16.-... in DC useage
9
Commissioning
Before commissioning, ensure that:
X
the device has been installed in accordance with the standards,
X
the connections have been correctly made,
X
the device is not damaged,
X
all screws and nuts are fully tightened.
10 Servicing
10.1 Maintenance
The following items must be checked as part of the maintenance schedule:
X
Check that no cable connections are loose.
X
Check the plastic enclosure for cracks or other visible signs of damage.
X
Check that the permitted temperatures, in accordance with IEC/EN 60079-0, are ad-
hered to.
X
Check the reset function of the switch lever.
X
Check that the device functions correctly.
Maintenance Intervals
Check explosion-protected components regularly to ensure that its fitting, installation and
operation are in accordance with the regulations.
Refer to the corresponding national regulations (e.g. EN 60079-14) for the type and
scope of tests. The maintenance intervals must be chosen, such that the occurrence of
deficiences, anticipated in the system, can be avoided.
Note the following when establishing the intervals between checks:
12218E00
12219E00
12220E00
12221E00
Auxiliary contact 1 NO
Fault indication contact 1 NO
Auxiliary contact 1 CO
Fault indication contact 1 CO
Remote trip
Undervoltage trip
Maintenance and repair work on the devicess may only be carried out by appropriately
authorized and trained personnel.
Before any work commences, the devices must be disconnected from the supply.
)
Observe the relevant national regulations in the country of use!
Schematic
05
08
98
95
05
95
08
98 06
96
C2
C1
U>
D1
D2
U<
Summary of Contents for 8562 Series